Description
ZP752-2 Addressable Sounder interface
ZP Loop interface providing two monitored circuits for driving conventional sounders.
Requires a 24VDC supply (can be taken from the ZP control panel or an external power supply)
Bi-colour LED status indicator (Red - Fire, Amber - Fault)
Output rating: 1 Amp 24V DC
Outputs programmable for Pulsed or Continuous operation
EN54 part 18 approved and CPD certified
Surface mount enclosure
IP rating: IP42
Dimensions (mm): 120w x 120h x 40d