Description
Analogue LHD Control Unit - PC Programmable
Alarmline II Analogue control unit provided with an LED indications only and requires laptop and configuration software for programming
Sensor cable length - Min 30.5m, Max 500m
Supply voltage: 20-28VDC, Current consumption: Quiescent - 70mA max, Alarm - 100mA max
2 x Volt free outputs (Alarm & Pre-Alarm) rated 2A @ 30VDC, 0.25A @ 250VAC
1 x Opto Isolated output (Fault) rated 20mA @ 50VDC
1 x Isolated input (Reset) requires 20-28VDC pulse for min 5s
Alarm and Pre-Alarm temperature range 54 - 100 Deg C (129 - 212 Deg F)
4 LED indicators: Red - Alarm, Red, Pre-Alarm, Amber - Fault, Power - Green
Polycarbonate enclosure, Ingress rating IP66
Dimensions (mm): 182w x 182h x 90d
Note: Requires AACU-PCC software - ordered separately