The C-TEC FF502P is a sounder circuit extender that adds four extra monitored conventional sounder circuits to a fire alarm system. It works with most manufacturers' fire alarm control panels. When the host panel's sounder circuit activates, the FF502P's four circuits follow it. If an open or short circuit is found on any extender circuit, the fault is reported back to the host panel.
Key features
- Four extra conventional sounder circuits with open and short circuit fault monitoring
- Compatible with most manufacturers' fire alarm control panels
- Basic connection needs four wires: 24V DC, 0V, Sounder -Ve and Sounder +Ve
- Only three control wires are needed with C-TEC conventional panels
- 24V DC can come from the host panel or an external PSU
- Supplied on a double gang plate for standard UK 25mm flush or surface back boxes
Technical specifications
- Supply voltage: 15-30V DC
- Quiescent current: less than 5mA at 27V DC
- Sounder circuits: 4
- Output current: 400mA max per circuit, 1A max total
- EOL resistors: 4 x 6k8 0.25W
- Dimensions: 146mm (W) x 85mm (H) x 23mm (D)
- Construction: white PVC plate, light grey label
- IP rating: IP40
- Weight: 124g
- Operating temperature: -10°C to +60°C