The Fike Twinflex Hipoint (302-0004) is an IP55 2-wire, zone-powered sounder for Fike Twinflex fire alarm systems, suitable for weather-exposed locations.
It gives audible indication when the system goes into alarm and can be mixed on the same zone as Twinflex multipoint detectors and other Twinflex devices.
Key features
- Zone-powered sounder for Twinflex 2-wire systems
- DIL switch selection of sound level (high/low) and pattern: dual tone UK evacuate, slow whoop or dual tone French warble
- Built-in end-of-line function, enabled by DIL switch on the last device
- IP55 housing with rubber seal; front fixed with four screws
Technical specifications
- Part number: 302-0004
- Dimensions: 123 x 130 x 101 mm
- Sound output: high 90+ dB(A); low 65+ dB(A)
- Voltage: 25.5 to 35 V DC (mains-powered panel); 20 to 26 V DC (battery-powered panel)
- Current: quiescent 185 µA; alarm high 14.5 mA, low 12.6 mA
- Loading: high 2.5 SLU / 14.5 DLU; low 2.0 SLU / 13.0 DLU (V3 / Pro and Pro² panels)
- Operating temperature: -10°C to +50°C
- IP rating: IP55 (not EN 54-3 compliant at this rating)
- Flammability: UL94-V2
- Cable: 2-core 1.5 mm² screened fire-resistant, radial circuit