The Xtralis VESDA VLI-880 is the VESDA VLI (Laser Industrial) aspirating smoke detector, an early warning ASD system designed to protect industrial applications and harsh environments of up to 2,000 m².
It combines a fail-safe, fully monitored Intelligent Filter with a clean-air barrier for optics protection, giving absolute detection and a long chamber life without re-calibration. The VLI is supported by Xtralis ASPIRE, VSC and VSM4 software and is compatible with existing VESDA installations. (The VLI-885 variant adds VESDAnet.)
Key features
- Robust IP66 enclosure, protected against dust and strong water jets, often removing the need for an external IP enclosure
- Up to 4 inlet pipes and up to 360 m total pipe length
- Intelligent Filter, lint trap, sub-sampling probe (inertial separator) and secondary filter reduce nuisance alarms and extend detector life
- Clean Air Zero, referencing and AutoLearn smoke and flow
- Ultrasonic flow sensing and air-path monitoring
- Five relays (Fire, Fault and 3 configurable), latching or non-latching; expandable GPI and relays
- Five high-intensity status LEDs and a local USB configuration port
- Imperial and metric pipe ports; modular field-replaceable parts
- Suitable for Class 1 Division 2 applications (Groups A, B, C and D); SIL 2 as per IEC 61508
- Approvals include EN 54-20 (Class A 24 holes, Class B 28 holes, Class C 60 holes), LPCB, FM, CE, UKCA, NF and ActivFire
Technical specifications
- Part number: VLI-880 (VESDA VLI)
- Supply voltage: 18–30 VDC
- Power consumption @ 24 VDC: 10 W nominal, 10.5 W in alarm (415 mA / 440 mA)
- Fuse rating: 1.6 A
- Maximum coverage: 2,000 m²
- Total pipe length: 360 m; maximum single pipe length: 120 m
- Minimum total airflow: 40 l/min; minimum airflow per pipe: 20 l/min
- Pipe: 25 mm external diameter, 15–21 mm internal diameter
- Relays: 5, rated 2 A @ 30 VDC – Fire (NO), Fault (NC), Configurable (NO)
- Sensitivity range: 0.05–20.0% obs/m
- Configurable general input (5–30 VDC): external reset, mains OK, standby, isolate, night-time threshold and more
- Event log: up to 18,000 events
- Ambient operating temperature: 0 °C to 38 °C; sampled air: -20 °C to 60 °C; humidity 10–95% RH non-condensing
- IP rating: IP66; cable access: 4 x 25 mm entries
- Dimensions (WHD): 426.5 x 316.5 x 180 mm; weight: 6.035 kg