The Xtralis VESDA Sensepoint XCL Large Bore (XCL-LB-CO2PP-RM) is an aspirated carbon dioxide (CO2) gas detector that fits in-line in a standard aspirating smoke detection (ASD) pipe network, with Modbus RTU output and relays. It uses the airflow in the pipe to deliver multi-point gas sampling, giving gas detection for occupant protection and process monitoring alongside fire protection.
Key features
- Carbon dioxide (CO2) sensor, 1000 to 5000 ppm
- Modbus RTU output plus 2 configurable relays (alarm, fault)
- Multi-point aspirated sampling through the ASD pipe network for greater coverage than a fixed point detector
- Remote sampling: the detector can sit outside the protected zone for safe, convenient servicing
- Integral alarm status LEDs and gas port for bump testing and calibration
- Field-replaceable gas sensor cartridge
- Bluetooth pairing with the Sensepoint app for commissioning and maintenance
- Modbus version can be monitored in Xtralis VSC and VSM4, and networked to the Sensepoint 301C gas controller for extra relays
Technical specifications
- Part number: XCL-LB-CO2PP-RM
- Gas / range: Carbon dioxide (CO2), 1000 to 5000 ppm
- Output: Modbus RTU + 2 relays
- Maximum power consumption: 1.2 W (CO2) (relay version adds 0.6 W)
- Spare filter: XCL-LB-FLT-1 (pack of 10)
- Supply voltage: 24 V DC nominal (11 to 32 V DC analogue; 9 to 32 V DC Modbus) or 20 to 27 V AC
- Pipe compatibility: ASD pipe networks of 25 mm and 27 mm OD
- Dimensions (W x H x D): 113 x 113 x 59 mm
- Weight: 500 g
- Casing: polycarbonate
- Ingress protection: IP65, Type 4 (NEMA 250)
- Operating temperature: -20 to +50°C; humidity 0 to 99% RH non-condensing
- Relay outputs: 2 relays (24 V DC / 250 V AC, 5 A)
- Approvals: EN/UL/IEC 61010-1, CSA-C22.2 No. 61010-1-12, CE EMC (EN 50270), RED, FCC, BT SIG, UL2075 (CO and CH4), AS 1668.2