Shop all C-TEC

C-Tec XFP508X Mk1 Loop Powered Hush Bttn, XP95/Disc

SKU: XFP508XBrand: C-TEC
4.6store rating from 122 reviews
Stock available Qty Delivery
Poole0None in Poole
UK Hub101 to 3 working days
Need help choosing? Our UK team can check compatibility, stock and project pricing for you. 0117 440 4505info@jemsystems.co.uk
Price:
Sale price$85.00
102.00 inc. VAT85.00 ex VAT
Stock:
In stock (10 units)
Delivery
1 to 3 working days
Ships from our UK supplier hub
Collect in Poole
Not stocked in Poole
Delivery only
C-Tec XFP508X Mk1 Loop Powered Hush Bttn, XP95/Disc $85.00
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
American Express Apple Pay Google Pay KlarnaMaestroMastercard PayPalShop Pay Visa
Key featuresFull details
  • 2-minute silence and 15-minute isolate facilities to BS 5839-6
  • Sits on the communal addressable fire panel's loop and reports its status to the host panel
  • Own conventional detector circuit, conventional sounder circuit and loop isolator
  • Fully monitored for open and short circuit faults
  • Powered from the analogue loop
  • Selectable 12.5mA, 20mA or 30mA alarm current (up to 20 hush buttons per loop, depending on loop drive current)

Product details

The C-TEC XFP508X is a Mk1 loop-powered hush button for C-TEC XFP and ZFP addressable fire panels using the Apollo XP95/Discovery protocol. It sits on the communal fire panel's loop and gives an individual flat, apartment or HMO dwelling its own 2-minute silence facility (to BS 5839-6/12.2b) and 15-minute isolate facility (to BS 5839-6/12.2a). It reports its status back to the host panel.

Key features

  • 2-minute silence and 15-minute isolate facilities to BS 5839-6
  • Sits on the communal addressable fire panel's loop and reports its status to the host panel
  • Own conventional detector circuit, conventional sounder circuit and loop isolator
  • Fully monitored for open and short circuit faults
  • Powered from the analogue loop
  • Selectable 12.5mA, 20mA or 30mA alarm current (up to 20 hush buttons per loop, depending on loop drive current)
  • Helps reduce false alarms and unnecessary building evacuations
  • Mounts on a standard UK 25mm double gang back box

Technical specifications

  • Order code: XFP508X
  • Protocol/compatibility: C-TEC XFP/ZFP XP95/Discovery addressable fire panels (uses 2 addresses)
  • Power requirements: 22-40V DC (from the host panel's Apollo XP95/Discovery loop)
  • Quiescent current: 5mA
  • Detector zone circuits: 1 (max. 100m; max. 10 devices, any mix of detectors and manual call points)
  • Call point resistor: 330Ω (one supplied in the accessory pack)
  • Conventional sounder circuits: 1 (max. 100m; max. output current 30mA)
  • EOL resistor: 6800Ω
  • Alarm current: 30mA, 20mA or 12.5mA (selectable)
  • Indicators: Supply present, local alarm, hushed and fault LEDs
  • Dimensions: 146 W x 85 H x 21 D mm on a double gang plastic plate
  • IP rating: IP40
  • Weight: 120g
  • Operating conditions: -5ºC to +40ºC, max. 95% relative humidity