The Li-ion Tamer LT-ACC-PWR-12 is the 12 VDC DIN-rail power supply for the Li-ion Tamer GEN 3 lithium-ion battery off-gas detection system, which detects the venting of battery electrolyte solvent vapours that occurs early in a lithium-ion cell failure so that mitigation can take place before thermal runaway.
The 12 VDC supply is typically used to power the controller, Direct Power hubs, standard Ethernet switches and relay modules; the PoE Ethernet switches need the 48 VDC supply instead.
Key features
- 12 VDC, 10 A output for Li-ion Tamer GEN 3 components
- Wide 90 to 264 VAC input
- DIN-rail mountable (TS35/7.5 and TS35/15)
- A terminal cover for the AC input terminals is included in the LT-ACC-SAK spare accessory kit
Technical specifications
- Part number: LT-ACC-PWR-12 (Power Supply, 12VDC)
- Output: 12 VDC, 10 A rated
- Input: 90 to 264 VAC, 47 to 63 Hz
- AC current: 2.25 A at 115 VAC; 1.3 A at 230 VAC
- Operating temperature: -20 to +70°C
- Operating humidity: 20 to 95% RH (non-condensing)
- Storage: -40 to +85°C, 10 to 95% RH
- Weight: 600 g
- Note: the Li-ion Tamer GEN 3 system is not fire detection or fire alarm equipment, so EN 54-4 power supply requirements do not apply