Shop all Notifier Europe

Notifier HOP-933-100 INSPIRE Loop Licence (CLIP Protocol)

SKU: HOP-933-100Brand: Notifier Europe
4.6store rating from 126 reviews
Out of stock Qty Delivery
All locations0Lead time 2 to 6 weeks, estimate only
Need help choosing? Our UK team can check compatibility, stock and project pricing for you. 0117 440 4505info@jemsystems.co.uk
Price:
Sale price£253.40
304.08 inc. VAT253.40 ex VAT
Stock:
Out of stock. Lead time 2 to 6 weeks, estimate only
Delivery
Out of stock
Lead time 2 to 6 weeks, estimate only
Collect in Poole
Not stocked in Poole
Delivery only
Notifier HOP-933-100 INSPIRE Loop Licence (CLIP Protocol) £253.40
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
American Express Apple Pay Google Pay KlarnaMaestroMastercard PayPalShop Pay Visa
Key featuresFull details
  • Licences are bought and managed through the Honeywell Connected Life Safety Services (CLSS) cloud portal
  • Applied to a specific panel (by CPU serial number) as a .bin licence file, either online or offline with the CLSS configuration tool
  • An unlicensed INSPIRE panel shows a 'licence not found' message
  • On networked panels, disconnect each panel from the network before installing licences, then reconnect it
  • One CLIP licence is needed for each CLIP loop, so a dual loop module with both loops in CLIP mode needs two licences
  • OPAL and CLIP devices cannot be mixed on the same loop

Frequently bought together

Product details

The Notifier HOP-933-100 is a CLIP protocol loop licence for the Notifier INSPIRE E10/E15 fire alarm control panels. INSPIRE loops run the OPAL protocol by default. Each loop can be converted to legacy CLIP mode with a licence, so you can keep existing CLIP devices on the new panel.

INSPIRE is a modular, networkable fire alarm control panel from Notifier by Honeywell. It comes in 10U (E10) and 15U (E15) enclosures, uses the OPAL digital loop protocol, supports legacy CLIP devices and is compliant with EN54-2, EN54-4 and EN54-13.

Key features

  • Licences are bought and managed through the Honeywell Connected Life Safety Services (CLSS) cloud portal
  • Applied to a specific panel (by CPU serial number) as a .bin licence file, either online or offline with the CLSS configuration tool
  • An unlicensed INSPIRE panel shows a 'licence not found' message
  • On networked panels, disconnect each panel from the network before installing licences, then reconnect it
  • One CLIP licence is needed for each CLIP loop, so a dual loop module with both loops in CLIP mode needs two licences
  • OPAL and CLIP devices cannot be mixed on the same loop

Technical specifications

  • Licence type: CLIP loop (1 loop)
  • CLIP loop capacity: up to 99 detectors and 99 modules
  • For: Notifier INSPIRE E10 and E15 panels

Datasheets & documents