The Xtralis VESDA VSP-002 is the display module for the VESDA VLP aspirating smoke detector, supplied as a spare. It gives real-time indication of the detector status and can be mounted in the detector, in a remote mounting box or in a 19" sub rack.
Key features
- 20-segment vertical bar graph with Fire 1, Action and Alert threshold indicators
- 2-digit numeric display (smoke level, Fire 1 threshold/sensitivity or zone number)
- High-intensity alarm LEDs and built-in sounder
- Comprehensive fault reporting (system, zone, urgent, power, network, airflow, filter)
- Four push buttons: Mode/Test, Silence, Reset and Isolate (can be disabled, except Silence)
- Several displays can show information from one detector in multiple locations
Technical specifications
- Part number: VSP-002 (VLP display module)
- Supply voltage: 18-30 VDC
- Power, module only, at 24 VDC: 1.6 W / 60 mA quiescent, 2.2 W / 80 mA in alarm
- Alarm indicators: high-intensity LEDs, 70° viewing angle
- Operating temperature: 0°C to 39°C; humidity 10-99% RH non-condensing
- Approvals: FM, VdS, ActivFire, CE, UKCA