Shop all Advanced
Advanced MX-5402VE 1-4 Loop Fire Panel c/w 2 Loop cards (Argus)
SKU: MX-5402VEBrand: Advanced
| Out of stock | Qty | Delivery |
|---|---|---|
| All locations | 0 | Lead time 2 to 6 weeks, estimate only |
Need help choosing?
Our UK team can check compatibility, stock and project pricing for you.
0113 518 0540info@jemsystems.co.uk
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
Key featuresFull details
- Argus Vega protocol support
- White backlit 240 x 64 graphical LCD with tactile alphanumeric keypad
- 20 programmable zonal LEDs with slide-in labels, plus 25 system LEDs
- 4 programmable function buttons with LED confirmation
- Up to 200 fire zones per panel by default, allowing full EN 54 compliance without additional hardware; up to 2,000 zones when networked
- Powerful cause-and-effect programming and enhanced trace diagnostics
Frequently bought together

Advanced
Advanced MX-5403 1-4 Loop Fire Panel c/w 3 Loop cards - Large (Apo/Hoch)
Sale price£2,156.85
Out of stock. Lead time 2 to 6 weeks, estimate onlyProduct details
The Advanced MX-5402VE is an MxPro 5 series 1-4 loop analogue addressable fire alarm control panel in the extended enclosure, supplied with two loop driver cards fitted, for use with Argus Vega protocol devices. Its cause-and-effect programming and trace diagnostics make it suitable for a wide range of sites, from small buildings to large, complex multi-area systems.
The panel can be expanded to 4 loops by adding one loop driver card per extra loop (MXP-568).
Key features
- Argus Vega protocol support
- White backlit 240 x 64 graphical LCD with tactile alphanumeric keypad
- 20 programmable zonal LEDs with slide-in labels, plus 25 system LEDs
- 4 programmable function buttons with LED confirmation
- Up to 200 fire zones per panel by default, allowing full EN 54 compliance without additional hardware; up to 2,000 zones when networked
- Powerful cause-and-effect programming and enhanced trace diagnostics
- Auto-learn, loop detection and on-board scope facility for easier commissioning and fault finding
- On-board Ethernet for AdvancedLive fire panel monitoring (UK and Ireland only)
- Dedicated USB and RS232 ports for direct PC or modem connection; programmable from the keypad or with PC-NeT-022 configuration software
- Integral P-Bus for system expansion with option cards
- Optional network card (MXP-503 standard or MXP-509 fault-tolerant) for peer-to-peer networking in a fault-tolerant loop or radial format
- Display configurable for virtually any language or character set, with installer's logo support
- 3-year warranty
Technical specifications
- Loops: 1-4 loop panel, 2 loop driver cards fitted
- Protocol: Argus Vega
- Devices per loop: Protocol dependent
- Loop current: 500mA per loop
- Fire zones: 200 per panel, 2,000 networked
- Sounder circuits: 4 x 1A programmable
- On-board relays: 2 x 1A 30V AC/DC programmable (10mA, 5V min), expandable to 4 with MXP-507
- Auxiliary supply: 1 x 24V 500mA
- Inputs: 1 x monitored programmable input; 8 volt-free programmable key switch inputs
- Total output current: 5A maximum (loops, sounders and auxiliary combined)
- Mains supply: 200-240V AC 47-63Hz (+10% / -15%), 1.4A max
- Charger: 2A, temperature compensated
- Ethernet: 10-Base-T / 100-Base-T (AdvancedLive connectivity, UK and Ireland only)
- Ports: 1 x RS232, 1 x USB B type
- Event log: 5,000 event and diagnostic plus 500 fire events
- Enclosure: Steel, IP30, RAL 7035
- Dimensions (H x W x D): 750 x 450 x 190mm
- Cable entries: 30 x top, 6 x top rear, 2 x bottom rear, 3 x bottom (20mm knockouts)
- Battery capacity: 24V 4Ah minimum, 24V 45Ah maximum internal, plus 1 x 24V 45Ah maximum external using the optional battery enclosure (batteries not included)
- Operating temperature: -5°C to 40°C
- Humidity: 95% RH max
- Approvals: EN 54-2, EN 54-4, EN 50130-4, EN 55032, EN 62368-1