The Apollo XPA-CB-14019-APO is an XPander wireless combined unit: an XPander multisensor detector (optical/heat) fitted to a sounder base, giving detection and audible alarm from one point with no cabling to the loop.
XPander is Apollo's wireless range: devices communicate with an XPander interface wired to an XP95 or Discovery loop, using a bi-directional monitored radio platform at 868MHz, and each device is recognised by the control panel like any wired loop device. It suits heritage and architecturally sensitive buildings, rapid retrofits and temporary systems where cabling is impractical.
Key features
- XPander multisensor detector (optical/heat)
- Optical/heat multisensor smoke detection (EN54-7)
- Integrated sounder with selectable volume (74dB(A) / 87dB(A))
- Wireless: bi-directional monitored radio platform
- Sounder self-test
- Approved to EN54-3, EN54-7 and EN54-25
Technical specifications
- Multisensor: thermally enhanced smoke detector; will not alarm from heat alone
- Detection: photo-electric light scattering plus heat sensitive thermistor, sampled every 4 seconds
- Detector supply: regulated 3V from radio base
- Alarm indicator: integral, 360° visibility
- Detector dimensions: 100mm diameter x 50mm height, 100g
- Operating temperature: -10°C to +50°C
- Humidity: 0% to 95% RH (no condensation)
- Material: white polycarbonate
- Sounder: 4 tone pairs including the Apollo tone; self-test sends a fault signal if the sounder fails
- Sound output: 74dB(A) low, 87dB(A) high
- Sounder batteries: one pack of 3 x AA and one pack of 3 x C alkaline, typical life 3-5 years
- Radio frequency: 868MHz
- Standards: EN54-3, EN54-7 and EN54-25