The Apollo XPA-HT-11171-APO is the XPander Heat Detector (CS) head: a static heat detector for Apollo's XPander wireless range. It fits the XPander address (wireless) module XPA-WB-10022-APO and is for areas where smoke detectors are unsuitable and a rate-of-rise (A1R) detector is not appropriate.
XPander is Apollo's wireless range: devices communicate with an XPander interface wired to an XP95 or Discovery loop, using a bi-directional monitored radio platform at 868MHz, and each device is recognised by the control panel like any wired loop device. It suits heritage and architecturally sensitive buildings, rapid retrofits and temporary systems where cabling is impractical.
Key features
- EN54-5 class CS static heat detector
- Open-web casing lets air flow freely across the thermistor
- Temperature measured every 2 seconds
- 360° alarm indicator
- Can be locked into the wireless module
Technical specifications
- Heat detector class: CS (static)
- Heat sensing: thermistor, sampled every 2 seconds
- Detector supply: regulated 3V from radio base
- Alarm indicator: integral, 360° visibility
- Detector dimensions: 100mm diameter x 30mm height, 80g
- Operating temperature: -10°C to +50°C
- Humidity: 0% to 95% RH (no condensation)
- Material: white polycarbonate
- Mounts in: XPander address (wireless) module XPA-WB-10022-APO
- Dimensions with wireless module: 113mm diameter x 81mm
- Standards: EN54-5, EN54-25