The C-TEC ZFP2L/X is a 2-loop ZFP touchscreen-controlled addressable fire alarm panel, supplied as the blank-module variant (Z41 touchscreen control module with ZBLANK blank modules, no additional zone LED or switch modules fitted). It drives Apollo XP95 and Discovery protocol detectors, call points and interfaces, and accepts standby batteries from 7Ah up to 38Ah.
Key features
- Touchscreen-controlled addressable fire panel from C-TEC’s ZFP range
- Rapid loop learn, flexible cause & effects and powerful system diagnostics
- Hi-integrity fault-tolerant RS485 networking option (optional ZHN card) for up to 64 network nodes
- Optional ‘A-Bus’ expansion PCBs, paging and graphics interface facilities
- Intuitive PC programming tools
- 2 Apollo XP95/Discovery compatible loop drivers
- Certified to EN54-2 & EN54-4 by Intertek
- Build your own configuration by adding C-TEC switch & indicator modules and A-Bus PCBs
Technical specifications
- Protocol: Apollo XP95/Discovery
- Number of loops: 2
- Battery charge capacity: 7Ah min. to 38Ah max.
- Max. battery size: 2 x 12V 38Ah VRLA (connected in series)
- Mains rated current: 1.35A max.
- Max. loop output current: 500mA (25V min.; 34V max.)
- Max. loop length: 1km
- Max. addressable devices per loop: 126
- Mains supply: 230V AC 50/60Hz
- Internal power supply: 27V DC nominal; total output current limited to 5A
- Conventional sounder circuits: 2 (max. 500m per circuit), 2 x 1A max. sounder output current; EOL resistor 6k8 (6800Ω)
- Auxiliary relays: 2 x programmable (from cause & effects) plus 1 x fault relay; volt-free single-pole changeover rated 1A at 30V DC
- Auxiliary power output: 24V (19.5V min., 28V max.), protected by a resettable fuse, 100mA max.
- Auxiliary inputs: 2 x programmable, connect to 0V to trigger, max. input voltage 27V (non-latching)
- Display: full-colour 480 x 272 pixel touchscreen with all relevant EN54 indicators plus 5 programmable indicators
- Controls: interactive touchscreen with menu-sensitive buttons; keyswitch for direct access to Access Level 2
- PC connection: galvanically isolated USB socket on the Z41 touchscreen control module
- Pager/DECT connection: RS232 (requires a BF874QAQ transmitter and BF877QAQ display pager as a minimum)
- Networking: RS485 hi-integrity multi-path fault-tolerant network via optional ZHN card, up to 64 nodes (panels and compact controllers)
- Expansion: RS485 peripheral bus for up to 15 ‘A-Bus’ PCBs
- Terminals: fixed, largest acceptable conductor size 1mm²
- Construction: light grey textured 1.2mm Zintec mild steel, RAL7035 epoxy paint
- IP rating: IP30
- Operating conditions: -5°C to +40°C, max. 95% relative humidity
- Graphics interface/diagnostics: RS485, Drax compatible
- Approvals: certified to EN54-2 & 4 by Intertek