The EMS FireCell FCX-170-001 is the wireless detector base for the FireCell wireless fire detection system. Fitted with a FireCell detector head, such as the FCX-177-001 optical smoke detector, it forms a wireless detector that is individually addressed at the fire control panel. It is compatible with the EMS FireCell system, including the Fusion RLM.
Key features
- Dual band 868MHz radio with auto-adjusting power output
- Individual addressing at the fire control panel
- Anti-tamper locking mechanism
- Supports the FasTest detector maintenance feature
- Third-party EN certified as part of the FireCell detector
- Note: supplied as the wireless base only; detector head sold separately
Technical specifications
-
Part number: FCX-170-001 (wireless detector base only)
-
Frequency: 868MHz, dual band
-
Radio range: Up to 1,250m (clear line of sight)
-
Output power: 0 to 14dBm (auto adjusting)
-
Signalling protocol: X
-
Batteries: 6 x AA alkaline (Panasonic LR6AD Powerline / Varta 4006 Industrial)
-
Dimensions (with optical detector): 113mm diameter x 76mm depth
-
Operating temperature: -10°C to 55°C
-
Ingress protection: IP23, indoor use only
-
Standards: EN 54-7 and EN 54-25 (with FCX-177-001 optical smoke detector)