FFE Fireray 5000 Detector, UL,FM (5000-031)
| Out of stock | Qty | Delivery |
|---|---|---|
| All locations | 0 | Lead time 2 to 6 weeks, estimate only |
- Motorised, auto-aligning reflective beam detector
- Integral laser for fast positioning of the reflector
- Auto-Align: automatic beam alignment after laser positioning
- Contamination compensation
- Easifit first-fix base
- Programmable sensitivity and fire thresholds, set from the System Controller
Product details
The FFE Fireray 5000 Detector (5000-031) is the UL/FM version of the motorised, auto-aligning reflective infrared beam smoke detector head for the Fireray 5000 system. The detector combines the infrared transmitter and receiver in one unit. It projects a beam to a reflective prism, and if smoke in the beam path reduces the returned signal below a pre-set level, it raises an alarm.
It connects to a low-level Fireray 5000 System Controller over a 2-wire interface. Each controller supports up to two detectors, with separate fire and fault relays for each. An integral laser allows quick coarse alignment, and Auto-Align then steers the beam into the optimum position automatically.
Key features
- Motorised, auto-aligning reflective beam detector
- Integral laser for fast positioning of the reflector
- Auto-Align: automatic beam alignment after laser positioning
- Contamination compensation
- Easifit first-fix base
- Programmable sensitivity and fire thresholds, set from the System Controller
- UL/FM version; Fireray 5000 approvals include EN54-12 and UL268
Technical specifications
- Part number: 5000-031 (UL/FM)
- Fireray 5000 operating distance: 8m to 100m between detector and reflector, depending on system version (4 reflectors required for operation over 50m)
- Maximum angular alignment of detector: ±3.5°
- Optical wavelength: 850nm
- Fault level (rapid obscuration within 2 seconds): 87%
- Operating voltage (to System Controller): 14 to 36V DC
- Operating current: 5.5mA typical with 1 detector; 8mA typical with 2 detectors; 36mA typical in alignment modes
- Response threshold: 10% to 60% (0.45 to 3.98dB), default 35%
- Delay to alarm and delay to fault: user settable, 2 to 30 seconds (default 10 seconds)
- Fire and fault relay contacts (VFCO): 0.1 to 36V DC, 0.1 to 100mA
- Cable, System Controller to detector: 2-core, up to 100m, 0.5 to 1.6mm (24 to 14 AWG)
- Operating temperature: -10°C to +55°C
- Storage temperature: -40°C to +85°C
- Relative humidity: up to 93% (non-condensing)
- IP rating: IP54
- Housing flammability rating: UL94 V0
- UL file: S3417
- Detector dimensions (including easy-fit base): 134 x 131 x 134mm (W x H x D)
- Detector weight: 0.5kg
Datasheets & documents