The Fike FIK-UV-IR-F-HD-AS11 is a UV/IR flame detector with high-definition video output, for fast, reliable detection of hydrocarbon fires (visible and non-visible) in all weather and light conditions. This version is for hydrocarbon fires only.
The integral HD camera gives clear images of the protected area, so responders can see the situation before entering. This version has M25 conduit openings.
Key features
- UV/IR detection of hydrocarbon fires; IR spectral response 4.0 to 5.0 microns
- Ultra-fast mode detects fireballs or explosions within 5 ms
- Detects a 0.1 m² n-heptane pan fire at up to 30 m
- UV and IR warning levels on the 0-20 mA output when elevated radiation is detected
- Automatic HD video recording of fire events, plus data/event logger in non-volatile memory
- Ethernet communication in addition to 0-20 mA and Modbus
- Automatic and manual built-in test of window cleanliness and overall operation
- Window heater to prevent condensation and icing
- Tilt mounting bracket (ordered separately) fits above or below the detector
Technical specifications
- Part number: FIK-UV-IR-F-HD-AS11 (hydrocarbon fire only, M25 conduit openings)
- Detection: 5 ms for fast burst of explosion; <4 s for 0.1 m² n-heptane pan fire at 0 to 30 m
- Field of view (IR): 90° horizontal, 80° vertical
- Time delay: 0 to 30 seconds
- Built-in test: automatic or manual
- HD video: clear imaging of fire and people at 30 m; records 1 minute pre-event and 3 minutes post-event; ONVIF Profile S
- Operating voltage: 24 VDC nominal (18 to 32 VDC)
- Current consumption: standby 180 mA; maximum 250 mA (including window heater)
- Outputs: alarm (normally open) and fault (normally closed) relays rated 2 A at 30 VDC; 0-20 mA stepped current output; Modbus RTU on RS-485; Ethernet IEEE 802.3 10Base-T; composite video (NTSC or PAL)
- Conduit entries: 2 x M25 x 1.5
- Wiring: 12 to 20 AWG (2.5 to 0.35 mm²)
- Size: 200 x 130 x 130 mm
- Weight: detector (stainless steel) 4.4 kg
- Operating temperature: -55°C to +75°C (option to +85°C)
- Humidity: up to 99% RH, non-condensing
- Ingress protection: IP66 and IP68; NEMA 4X and 6P
- Approvals: ATEX, IECEx and FM/FMC explosion proof; performance to ANSI FM 3260 and EN 54-10