The Global Fire Equipment VULCAN 2 CS is a low-consumption conventional base sounder, supplied with a lid. It can be used as an unobtrusive, low-profile sounder on its own (with the lid fitted) or as a detector base with an integrated sounder, installed with a conventional detector. Combining the sounder and detector in one location reduces installation costs and improves the appearance of the fire alarm system. Four tones are selectable by jumpers and the sound level can be adjusted with a potentiometer.
Key features
- Conventional base sounder: use with a conventional detector, or stand-alone with the lid
- Low-profile, unobtrusive design
- Four jumper-selectable tones
- Adjustable sound level via potentiometer
- Low current consumption
- Certified 1328-CPR-0289
Technical specifications
- Product code: VULCAN2-CS
- Supply voltage: 20V to 30V DC
- Tones and current: sweeping 800-1000 Hz (2.5mA); alternating high frequency 2.7-3.2 kHz (5mA); continuous 800 Hz (2.5mA); alternating low frequency 800-1000 Hz (2.5mA)
- Max. sounder output: 98 dB at 1 m (30V DC)
- Cable size: 0.5-2.5mm²
- Operating temperature: -10°C to 55°C
- Max. humidity: 95% RH non-condensing
- Case material: ABS
- Protection: IP21C, Type A, indoor use
- Dimensions: 110 mm (D) x 29 mm (H); 37.5 mm (H) with lid
- Weight: 149 g with lid
For EN 54-13 compliance, check the control panel manual specifications.