Notifier Europe 020-538 ID3000 Basic Equipment Kit, 2, 8 loops
SKU: 020-538Brand: Notifier Europe
| Available to order | Qty | Delivery |
|---|---|---|
| Pre-order | 0 | Lead time 2 to 6 weeks |
Notifier Europe 020-538 ID3000 Basic Equipment Kit, 2, 8 loops
£1,570.75
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
Key featuresFull details
- 2 analogue addressable loops as standard, expandable to 8
- Up to 198 devices per loop (99 detectors + 99 modules/sounders)
- Up to 255 fire zones per panel
- Peer-to-peer ID²net networking of up to 63 panels (requires NGM 020-647)
- 9 sensitivity levels per smoke sensor, configurable by time of day or day of week
- Auto-learn of loops, walk test and double address detection
Frequently bought together

Notifier Europe
Notifier Europe 020-543 Dual Transmission Path Board Kit
Sale price£502.50
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

Notifier Europe
Notifier Europe 020-548 Optional Status Indication Board Kit for 7A PSU
Sale price£161.75
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

Notifier Europe
Notifier Europe 020-549 ID3000 Intelligent Dual Loop Board Kit (E-LIB)
Sale price£483.40
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

Notifier Europe
Notifier Europe 020-553 RS485 Communication Card Kit for ID50 & ID60
Sale price£135.30
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

Notifier Europe
Notifier Europe 020-569 ID2000/ID3000 CPU PCA Kit
Sale price£744.15
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.
Product details
The 020-538 is the ID3000 basic equipment kit, which forms the core of a Notifier ID3000 modular addressable fire alarm control panel. It includes the main chassis with a hinged display, the base PCB with two loop interfaces, and the microprocessor PCB with the panel software. Add dual loop cards to expand from 2 to 8 loops. The back box, cover and power supply are ordered separately.
Key features
- 2 analogue addressable loops as standard, expandable to 8
- Up to 198 devices per loop (99 detectors + 99 modules/sounders)
- Up to 255 fire zones per panel
- Peer-to-peer ID²net networking of up to 63 panels (requires NGM 020-647)
- 9 sensitivity levels per smoke sensor, configurable by time of day or day of week
- Auto-learn of loops, walk test and double address detection
- CPD approved by LPCB (BRE) and VdS
Technical specifications
- Loops: 2 (expandable to 8 with 020-588/020-549 cards)
- Loop output voltage: 22.5 to 26.4 V
- Loop maximum load: 0.5 A
- Outputs: 2 sounder, 2 sounder/volt-free selectable, 2 volt-free (common fire and fault), 2 x 24 V DC auxiliary
- Operating temperature: -5°C to +45°C
- Relative humidity: 5% to 95% non-condensing
- Ingress protection: IP30 (EN 60529)
- Mains supply: 230 V AC +/-15%, 50 Hz (via external double-pole isolator)
What's in the box
- Main chassis assembly with hinged display
- Base PCB with two loop interfaces
- Microprocessor PCB with software
- Spare fuses