The Notifier ECO1002 A is a conventional multi-criteria smoke and heat detector from the System Sensor ECO1000 range. It combines an optical smoke chamber and a thermal element with a microprocessor running detection algorithms.
Using both smoke and heat gives a faster response to real fires and reduces the risk of unwanted alarms. It is for conventional fire alarm zones and fits the ECO1000 base range.
Key features
- Photoelectric smoke plus thermal sensing
- Automatic drift compensation
- Approved to EN54-7:2000 (A1) and MED 96/98/EC
- Integral LED that latches on in alarm until reset by a momentary power interruption
- Optional remote LED output
- Remote alarm test using the ECO1000RTU laser test unit
- Operates on 12 V and 24 V systems
- Fits ECO1000 series bases (standard, deep, resistor, Schottky diode and relay versions)
Technical specifications
- Operating voltage: 8 to 30 V DC (12/24 V DC nominal)
- Maximum standby current: 75 µA at 24 V DC (25°C)
- Maximum permissible alarm current: 80 mA (limited by control panel)
- Application temperature range: -30°C to +70°C
- Humidity: 0 to 95% RH (non-condensing)
- Height: 40.5 mm (plus 9.5 mm for standard base)
- Diameter: 102 mm
- Weight: 78 g (plus 45 g for standard base)
- Terminal wire gauge: 0.4 mm² to 2.0 mm²
- Colour: approximately RAL 9016
- Material: ABS