Advanced GO1+ Fire Alarm Panel - Grey (Apollo/Hochiki - 126/127 Addresses)
| Stock available | Qty | Delivery |
|---|---|---|
| Poole | 0 | None in Poole |
| UK Hub | 41 | 1 to 3 working days |
- Apollo (Discovery, XP95) and Hochiki (ESP) protocol support, up to 126 addresses (Apollo) / 127 addresses (Hochiki)
- Graphical LCD user interface with LED indicators and push buttons
- Integral 15 zone LEDs for BS 5839 compliance, plus 35 additional software indication zones
- Auto-learn, loop detection and on-board scope facility for installation and fault finding
- 500 fire + 5,000 general event logging with advanced diagnostics
- Two on-board sounder outputs and three on-board relay outputs
Frequently bought together




Product details
The Advanced GO1+ is a Go+ series single-loop addressable fire alarm control panel in grey, for Apollo (Discovery, XP95) and Hochiki (ESP) protocol devices, with a maximum of 126 addresses (Apollo) / 127 addresses (Hochiki). The Go series is designed for non-networked single-loop fire alarm systems, combining an ergonomic control layout with a high-resolution, high-contrast graphical LCD and tactile keypad for select-and-click programming.
Integral zonal LEDs give instant identification of alarm locations and help achieve BS 5839 compliance without the cost of a separate LED zone card. Cause-and-effect programming and trace diagnostics make it suitable for small to medium systems.
Key features
- Apollo (Discovery, XP95) and Hochiki (ESP) protocol support, up to 126 addresses (Apollo) / 127 addresses (Hochiki)
- Graphical LCD user interface with LED indicators and push buttons
- Integral 15 zone LEDs for BS 5839 compliance, plus 35 additional software indication zones
- Auto-learn, loop detection and on-board scope facility for installation and fault finding
- 500 fire + 5,000 general event logging with advanced diagnostics
- Two on-board sounder outputs and three on-board relay outputs
- Optional 3 monitored inputs/outputs for fire/fault routing (with P-Bus adaptor and routing card) for full EN 54 compliance when connected to an alarm receiving centre
- Dedicated USB Type B port for direct PC connection; programmable on site from the panel or with the PC Configuration Tool
- 'No hinge' removable door and hangable chassis for easier installation
- Meets EN 54-13 (2005) clauses 5.3.4.1 and 5.3.4.2 (partial open and short circuits)
- New PCB integrates control panel and peripherals on one board, for 9 times faster operation than MxPro 4
Technical specifications
- Protocol: Apollo (Discovery, XP95) and Hochiki (ESP)
- Maximum addresses: 126 addresses (Apollo) / 127 addresses (Hochiki)
- Number of loops: 1
- Loop current: 500mA max
- Number of fire zones: 50 max
- Sounder outputs: 2 x 1A programmable (1A total)
- Relay outputs: 3 x 1A 30V AC/DC (max) to 10mA 5V (min), programmable
- Auxiliary output: 24V DC, 100mA (with GOP-001 fitted)
- Display: White backlit 240 x 64 graphical LCD
- Programmable inputs: 1 x key switch, 1 x monitored
- USB: USB type B for PC connection
- Ethernet: 10-Base-T, 100-Base-T
- Event log: 5,000 events with diagnostics + 500 fire events
- Enclosure: Steel, IP30, RAL 7035
- Dimensions (H x W x D): 345 x 345 x 87mm
- Weight (excluding batteries): 4kg
- Cable entries: 14 x 20mm knockouts at top
- AC supply: 220-240V, 50-60Hz, 1.0A max
- Power supply: On-board 24V DC 1.5A high-efficiency off-line switched mode
- Battery capacity: 24V 4Ah (min) to 24V 7Ah (max), internal
- Charging current: 0.35A, temperature compensated
- Deep discharge cut-off: 19.5V
- Operating temperature: -5°C to 40°C
- Humidity: 95% RH max
- Approvals: EN 54-2:1997+A1:2006; EN 54-4:1997+A1:2002+A2:2006
- Options: GOP-001 P-Bus adaptor card; GOP-002 access enable key switch assembly; MXP-532 routing/protection interface; MXP-506 routing termination card