Key featuresFull details
  • 19-inch rack-mount module assembly with industry-standard U spacing, RAL 7035
  • Nittan Evolution protocol support
  • White backlit 240 x 64 graphical LCD with tactile alphanumeric keypad
  • 20 programmable zonal LEDs with slide-in labels, plus 25 system LEDs
  • 4 programmable function buttons with LED confirmation
  • Up to 200 fire zones per panel by default, allowing full EN 54 compliance without additional hardware; up to 2,000 zones when networked

Frequently bought together

Product details

The Advanced MX-5404NR is an MxPro 5 series 1-4 loop analogue addressable fire alarm control panel in the 19-inch rack-mount format, supplied with four loop driver cards fitted, for use with Nittan Evolution protocol devices. Its cause-and-effect programming and trace diagnostics make it suitable for a wide range of sites, from small buildings to large, complex multi-area systems.

The MxPro 5 R series houses the panel as a module assembly designed to be installed in a standard 19-inch rack enclosure, making it ideal where an IP55 rating or a modular assembly of fire panels, switches and mimics in a 19-inch rack system is required.

Key features

  • 19-inch rack-mount module assembly with industry-standard U spacing, RAL 7035
  • Nittan Evolution protocol support
  • White backlit 240 x 64 graphical LCD with tactile alphanumeric keypad
  • 20 programmable zonal LEDs with slide-in labels, plus 25 system LEDs
  • 4 programmable function buttons with LED confirmation
  • Up to 200 fire zones per panel by default, allowing full EN 54 compliance without additional hardware; up to 2,000 zones when networked
  • Powerful cause-and-effect programming and enhanced trace diagnostics
  • Auto-learn, loop detection and on-board scope facility for easier commissioning and fault finding
  • On-board Ethernet for AdvancedLive fire panel monitoring (UK and Ireland only)
  • Dedicated USB and RS232 ports for direct PC or modem connection; programmable from the keypad or with PC-NeT-022 configuration software
  • Integral P-Bus for system expansion with option cards
  • Optional network card (MXP-503 standard or MXP-509 fault-tolerant) for peer-to-peer networking in a fault-tolerant loop or radial format
  • Display configurable for virtually any language or character set, with installer's logo support
  • 3-year warranty

Technical specifications

  • Loops: 1-4 loop panel, 4 loop driver cards fitted
  • Protocol: Nittan Evolution
  • Devices per loop: Protocol dependent
  • Loop current: 500mA per loop
  • Fire zones: 200 per panel, 2,000 networked
  • Sounder circuits: 4 x 1A programmable
  • On-board relays: 2 x 1A 30V AC/DC programmable (10mA, 5V min), expandable to 4 with MXP-507
  • Auxiliary supply: 1 x 24V 500mA
  • Inputs: 1 x monitored programmable input; 8 volt-free programmable key switch inputs
  • Total output current: 5A maximum (loops, sounders and auxiliary combined)
  • Mains supply: 200-240V AC 47-63Hz (+10% / -15%), 1.4A max
  • Charger: 2A, temperature compensated
  • Ethernet: 10-Base-T / 100-Base-T (AdvancedLive connectivity, UK and Ireland only)
  • Ports: 1 x RS232, 1 x USB B type
  • Event log: 5,000 event and diagnostic plus 500 fire events
  • Mounting: Module assembly for standard 19-inch rack enclosures; Advanced MXM-510 16U and 20U rack enclosures are listed as separate options (IP55 with the outer door closed, IP30 with the door open)
  • Operating temperature: -5°C to 40°C
  • Humidity: 95% RH max
  • Approvals: EN 54-2, EN 54-4, EN 50130-4, EN 55032, EN 62368-1
·