The Apollo XPA-CB-14018-APO is an XPander wireless combined unit: an XPander heat detector (class CS, static) fitted to a sounder base, giving detection and audible alarm from one point with no cabling to the loop.
XPander is Apollo's wireless range: devices communicate with an XPander interface wired to an XP95 or Discovery loop, using a bi-directional monitored radio platform at 868MHz, and each device is recognised by the control panel like any wired loop device. It suits heritage and architecturally sensitive buildings, rapid retrofits and temporary systems where cabling is impractical.
Key features
- XPander heat detector (class CS, static)
- EN54-5 CS heat detection
- Integrated sounder with selectable volume (74dB(A) / 87dB(A))
- Wireless: bi-directional monitored radio platform
- Sounder self-test
- Approved to EN54-3, EN54-5 and EN54-25
Technical specifications
- Heat detector class: CS (static); for areas where A1R is unsuitable
- Heat sensing: thermistor, sampled every 2 seconds
- Detector supply: regulated 3V from radio base
- Alarm indicator: integral, 360° visibility
- Detector dimensions: 100mm diameter x 30mm height, 80g
- Operating temperature: -10°C to +50°C
- Humidity: 0% to 95% RH (no condensation)
- Material: white polycarbonate
- Sounder: 4 tone pairs including the Apollo tone; self-test sends a fault signal if the sounder fails
- Sound output: 74dB(A) low, 87dB(A) high
- Sounder batteries: one pack of 3 x AA and one pack of 3 x C alkaline, typical life 3-5 years
- Radio frequency: 868MHz
- Combined unit dimensions: 147mm diameter x 86mm depth
- Standards: EN54-3, EN54-5 and EN54-25