| Available to order | Qty | Delivery |
|---|---|---|
| Pre-order | 0 | Lead time 2 to 6 weeks |
C-Tec FP4E 4 Zone economy fire panel C-TEC
£246.15
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
Key featuresFull details
- Four conventional detector zone circuits and two conventional sounder circuits
- Metal enclosure with lift-off lid and heavy-duty base connections
- Separate indicators for open and short circuit fault, sounder fault and battery/power supply fault
- Short circuit = fire facility (pre-1980 BS, no resistors in call points), selectable zone by zone
- Non-latching class change sounder output; latching fire and non-latching fault outputs via optional expansion loom
- Connections for repeaters and add-ons such as fault, fire and sounder delay relay modules and sounder extender kits
Frequently bought together

C-TEC
C-TEC Green Type B Disabled Refuge Outstation - Flush Mount (EVC302GF)
Sale price£145.60
In stock
C-TEC
C-TEC Green Type B Disabled Refuge Outstation - Surface Mount (EVC302GS)
Sale price£155.15
In stock
C-TEC
C-Tec H Range Electromagnetic Door Retainer 240V
Sale price£38.75
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

C-TEC
C-TEC H Range Electromagnetic Door Retainer 24V
Sale price£35.35
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.
Product details
The C-TEC FF384-3 is a 4 zone economy conventional fire alarm panel from C-TEC's FP range, in a metal enclosure. It is designed to comply with BS 5839-4 and works with most conventional fire detectors, including C-TEC's ActiV range. C-TEC states that this panel is not compliant with EN54-2/4 and should not be used in new UK or European installations.
Key features
- Four conventional detector zone circuits and two conventional sounder circuits
- Metal enclosure with lift-off lid and heavy-duty base connections
- Separate indicators for open and short circuit fault, sounder fault and battery/power supply fault
- Short circuit = fire facility (pre-1980 BS, no resistors in call points), selectable zone by zone
- Non-latching class change sounder output; latching fire and non-latching fault outputs via optional expansion loom
- Connections for repeaters and add-ons such as fault, fire and sounder delay relay modules and sounder extender kits
- Space for 2 x 12V 2.3Ah VRLA batteries
Technical specifications
- Order code: FF384-3
- Standard: designed to comply with BS 5839-4 (for head-out monitoring use 1 x BF378M per zone)
- Mains supply: 230V 50/60Hz, 185mA maximum
- Internal power supply: 27V nominal; total output current limited to 800mA
- Quiescent current: 50mA
- Batteries: 2 x 12V 2.3Ah VRLA in series
- Detector zones: 4 (maximum 500m per circuit); up to 20 detectors per zone (maximum detector current 2mA), no limit on manual call points
- Call point resistor value: 470 to 680Ω
- Sounder circuits: 2 (maximum 500m per circuit), 800mA total, fused at 1A
- End-of-line resistor: 6800Ω
- Auxiliary relay: 1 x on-board (1A, 30V DC, follows sounders)
- Controls: reset, resound, lamp test, evacuate, silence alarm, silence fault, S/C = fire, one-man test, zone isolate; keyswitch
- Repeaters: up to 3 per main panel, maximum cable length 200m
- Dimensions: 322 W x 267 H x 92 D mm
- Construction: metal lid and base
- IP rating: IP30
- Weight: 4.3kg
- Operating temperature: -5°C to +40°C, maximum 95% relative humidity