Shop all Fire Fighting Enterprises
FFE Fireray 5000 Controller, UL,FM (5000-003)
SKU: 5000-003Brand: Fire Fighting Enterprises
| Available to order | Qty | Delivery |
|---|---|---|
| Pre-order | 0 | Lead time 2 to 6 weeks |
FFE Fireray 5000 Controller, UL,FM (5000-003)
£457.50
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
Key featuresFull details
- Supports up to 2 detectors per System Controller
- Separate fire and fault relays for each detector
- 2-wire interface from System Controller to detector
- Starts the detector integral laser and Auto-Align
- Programmable sensitivity and fire thresholds
- Logs the 50 most recent events per detector
Frequently bought together

Fire Fighting Enterprises
FFE Fireray 5000 Cover Plate (5000-012)
Sale price£22.50
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

Fire Fighting Enterprises
FFE Fireray 5000 Detector (5000-048)
Sale price£380.25
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

Fire Fighting Enterprises
FFE Fireray 5000 Detector Surface Mount Uni-Box (5000-011)
Sale price£52.50
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

Fire Fighting Enterprises
FFE Fireray 5000 Detector, Long Range, UL,FM (5000-046)
Sale price£555.00
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

Fire Fighting Enterprises
FFE Fireray 5000 Detector, UL,FM (5000-031)
Sale price£487.50
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.
Product details
The FFE Fireray 5000 Controller (5000-003) is the UL/FM version of the low-level System Controller for the Fireray 5000 motorised, auto-aligning reflective beam smoke detector. It is mounted at an accessible height and connects to up to two Fireray 5000 detector heads over a 2-wire interface.
The controller has two pairs of fire and fault relays, one pair for each detector, for connection to the fire alarm system. It is used to start laser alignment and Auto-Align, set sensitivity and delays, and view the event log. It has 20mm cable gland knockouts for wiring.
Key features
- Supports up to 2 detectors per System Controller
- Separate fire and fault relays for each detector
- 2-wire interface from System Controller to detector
- Starts the detector integral laser and Auto-Align
- Programmable sensitivity and fire thresholds
- Logs the 50 most recent events per detector
- 20mm cable gland knockouts
- UL/FM version; Fireray 5000 approvals include EN54-12 and UL268
Technical specifications
- Part number: 5000-003 (UL/FM)
- Operating voltage (to System Controller): 14 to 36V DC
- Operating current: 5.5mA typical with 1 detector; 8mA typical with 2 detectors; 36mA typical in alignment modes
- Response threshold: 10% to 60% (0.45 to 3.98dB), default 35%
- Delay to alarm and delay to fault: user settable, 2 to 30 seconds (default 10 seconds)
- Fire and fault relay contacts (VFCO): 0.1 to 36V DC, 0.1 to 100mA
- Cable, System Controller to detector: 2-core, up to 100m, 0.5 to 1.6mm (24 to 14 AWG)
- Operating temperature: -10°C to +55°C
- Storage temperature: -40°C to +85°C
- Relative humidity: up to 93% (non-condensing)
- IP rating: IP54
- Housing flammability rating: UL94 V0
- UL file: S3417
- System Controller dimensions (including base): 202 x 230 x 87mm (W x H x D)
- System Controller weight: 1kg