| Out of stock | Qty | Delivery |
|---|---|---|
| All locations | 0 | Lead time 2 to 6 weeks, estimate only |
Need help choosing?
Our UK team can check compatibility, stock and project pricing for you.
0113 518 0540info@jemsystems.co.uk
Fike Twinflex Manual Call Point (No Cover) (402-0006-NC)
£21.50
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
Key featuresFull details
- Twinflex 2-wire device that mixes on the same zone as other Twinflex devices
- Resettable element that doesn't need replacing after operation
- Built-in end-of-line, enabled by DIL switch
- Surface mounting, or flush mounting in a standard single-gang box (minimum 47 mm internal depth) with the adaptor plate
- Supplied without cover (NC version)
Frequently bought together

Fike
Fike Twinflex Multipoint ASD Detector (Black) (204-0003-B)
Sale price£51.00
Out of stock. Lead time 2 to 6 weeks, estimate only
Fike
Fike Twinflex Multipoint ASD Detector with Sounder (Black) (204-0001-B)
Sale price£59.30
Out of stock. Lead time 2 to 6 weeks, estimate onlyProduct details
The Fike Twinflex Manual Call Point (402-0006-NC) is a 2-wire, zone-powered manual call point for Fike's Twinflex fire alarm system. It can share a zone with Twinflex Multipoint detectors, sounders and other Twinflex devices. This version is supplied without a call point cover. When operated, the resettable element latches into the alarm position until it is reset with the key.
Key features
- Twinflex 2-wire device that mixes on the same zone as other Twinflex devices
- Resettable element that doesn't need replacing after operation
- Built-in end-of-line, enabled by DIL switch
- Surface mounting, or flush mounting in a standard single-gang box (minimum 47 mm internal depth) with the adaptor plate
- Supplied without cover (NC version)
Technical specifications
- Dimensions (W x H): 87 x 87 mm
- Depth: 53 mm surface, 25 mm flush
- Voltage: 25.5 to 35 V DC (from mains-powered panel)
- Quiescent current: 50 µA typical
- Operating temperature: -10°C to +50°C
- Flammability: UL94-V2; IP21C
- Standard: EN 54-11