Fireblitz FBA-G2 Automatic 2kg Clean Agent Fire Extinguisher
| Out of stock | Qty | Delivery |
|---|---|---|
| All locations | 0 | Lead time 2 to 6 weeks, estimate only |
- Clean agent (Halon replacement) with zero ozone depletion
- Suitable for Class B and C fires
- Safe for use on electrical equipment
- Supplied with a powder-coated steel wire bracket
- 5-year warranty
- Choose the unit by the gross volume of the compartment; one unit should protect the whole compartment
Frequently bought together





Product details
The Fireblitz FBA-G2 is a 2kg automatic fire extinguisher using an ozone-friendly clean agent, protecting enclosed compartments up to 3.4m³ without manual operation.
The Fireblitz 2 kg Automatic Clean Agent Fire Extinguisher (FBA-G2) is an ozone-friendly automatic fire suppression unit. It protects enclosed spaces such as machinery and plant, boat and vehicle engine compartments, and sensitive areas holding high-value assets such as computing and telecoms equipment. It discharges automatically when the surrounding temperature reaches its activation point.
Key features
- Clean agent (Halon replacement) with zero ozone depletion
- Suitable for Class B and C fires
- Safe for use on electrical equipment
- Supplied with a powder-coated steel wire bracket
- 5-year warranty
- Choose the unit by the gross volume of the compartment; one unit should protect the whole compartment
Technical specifications
- Capacity: 2 kg
- Maximum volume protected: 3.4 m³
- Total weight: 3.60 kg
- Total height: 380 mm
- Total width (including bracket): 125 mm
- Working temperature: -20°C to +60°C
- Discharge: under 10 seconds at 79°C ± 5°C
- Operating pressure: 12 bar at 20°C
- Minimum burst pressure: 55 bar
- Mounting: discharge head at any angle below the horizontal; never pointing upwards; keep away from direct heat sources such as exhaust manifolds
Used for: engine compartments on boats and vehicles, machinery and plant enclosures, and cabinets holding computing and telecoms equipment.
Frequently asked questions
What volume does the FBA-G2 protect?
The maximum protected volume is 3.4 m³. Choose the unit by the gross volume of the compartment; one unit should protect the whole compartment.
When does it discharge?
It discharges automatically in under 10 seconds when the surrounding temperature reaches 79°C ± 5°C.
How should it be mounted?
The discharge head can be at any angle below the horizontal but must never point upwards, and the unit should be kept away from direct heat sources such as exhaust manifolds. A powder-coated steel wire bracket is supplied.