Shop all Honeywell
Honeywell FSL100-UVIR Flame UV/IR 25m Zone 2/22 Red
SKU: FSL100-UVIRBrand: Honeywell
| Available to order | Qty | Delivery |
|---|---|---|
| Pre-order | 0 | Lead time 2 to 6 weeks |
Honeywell FSL100-UVIR Flame UV/IR 25m Zone 2/22 Red
£2,236.35
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
Key featuresFull details
- UV/IR sensing with microprocessor signal analysis
- ATEX Zone 2/22 and FM Class 1, 2 & 3 Div. 2 (non-incendive)
- EN 54-10 Class 2 and FM 3260 performance approvals
- Red glass-reinforced polyester (GRP) housing: lightweight, impact and UV resistant
- Automatic and manual self-test
- Alarm and fault relays plus stepped 0-20 mA sink output
Frequently bought together

Honeywell
Honeywell Home R200C-1 10 Year Longlife Battery Carbon Monoxide Alarm
Sale price£29.65
In stock
Honeywell
Honeywell Home R200C-N1 10 Year Longlife Battery Radio-Interlink Carbon Monoxide Alarm
Sale price£50.50
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.
Product details
The Honeywell FSL100-UVIR is a combined ultraviolet and infrared (UV/IR) flame detector from the FSL100 series. It monitors an area for the invisible UV and IR radiation produced by flames and uses microprocessor signal analysis to decide whether a fire is present, even with sunlight, smoke, dust or vapour in view.
It connects to a conventional fire control panel via end-of-line and alarm resistors, to equipment that accepts relay outputs, or to a PLC with a 0-20 mA input. It is certified for ATEX Zone 2/22 hazardous areas and to EN 54-10.
Key features
- UV/IR sensing with microprocessor signal analysis
- ATEX Zone 2/22 and FM Class 1, 2 & 3 Div. 2 (non-incendive)
- EN 54-10 Class 2 and FM 3260 performance approvals
- Red glass-reinforced polyester (GRP) housing: lightweight, impact and UV resistant
- Automatic and manual self-test
- Alarm and fault relays plus stepped 0-20 mA sink output
- Selectable latching or non-latching alarm output
- Local green/yellow/red status LEDs
- Pressure-compensating element reduces moisture build-up
Technical specifications
- Supply: 12-24 V DC (10-28 V DC)
- Current: 25 mA normal, approx. 75 mA in alarm (at 24 V DC)
- Maximum range: 23 m to a 0.09 m² n-heptane fire (alarm in under 10 s)
- Cone of vision: 90°
- Alarm relay: SPDT, 30 V DC 2 A, 60 W max.
- Fault relay: SPDT, 30 V DC 2 A, 60 W max.
- Current output: 0-20 mA stepped (4 mA normal, 20 mA alarm)
- Ingress protection: IP65
- Operating temperature: -25 to +70 °C (ATEX/IECEx/FM); -40 to +70 °C (safe areas)
- Humidity: 0-95% RH non-condensing
- Dimensions (body): 125 x 80 x 57 mm
- Weight: 465 g (745 g with optional mount)