Shop all Notifier Europe
Notifier ECO1000BREL12L Relay Detector Base (12V, Latching)
SKU: ECO1000BREL12LBrand: Notifier Europe
| Available to order | Qty | Delivery |
|---|---|---|
| Pre-order | 0 | Lead time 2 to 6 weeks |
Notifier ECO1000BREL12L Relay Detector Base (12V, Latching)
£13.75
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
Key featuresFull details
- Plug-in relay base for System Sensor ECO1000 detector heads
- Works in 2-wire and 4-wire systems
- Normally open and normally closed relay contacts on a separate terminal block
- Built-in current limiting to the detector in alarm
- Relay driven directly by the detector
- Shorting spring for wiring continuity tests before detectors are fitted
Frequently bought together

Notifier Europe
Notifier ECO1000BREL12NL Relay Detector Base (12V, Non-Latching)
Sale price£5.65
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

Notifier Europe
Notifier ECO1000BREL24L Relay Detector Base (24V, Latching)
Sale price£21.70
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

Notifier Europe
Notifier ECO1000DBR Deep Detector Base (470 Ohm Resistor)
Sale price£7.60
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

Notifier Europe
Notifier ECO1002 A Conventional Optical Smoke and Heat Detector
Sale price£25.70
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

Notifier Europe
Notifier ECO1003 A Conventional Optical Smoke Detector
Sale price£18.45
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.
Product details
The ECO1000BREL12L is a 12 V latching relay base for System Sensor ECO1000 conventional detectors. When the detector goes into alarm the relay switches, and it stays latched until the supply to the detector and base is removed.
Key features
- Plug-in relay base for System Sensor ECO1000 detector heads
- Works in 2-wire and 4-wire systems
- Normally open and normally closed relay contacts on a separate terminal block
- Built-in current limiting to the detector in alarm
- Relay driven directly by the detector
- Shorting spring for wiring continuity tests before detectors are fitted
- Tamper-resist feature stops the detector being removed without a tool
- Latching: alarm is cleared only by removing the supply
- Devices connected to the contacts should not signal an alarm until the contacts have switched for more than 500 ms (prevents nuisance alarms from shock or vibration)
Technical specifications
- Supply voltage: 9.5 to 15 V DC
- Standby current: 1 µA
- Contact rating: 1 A DC
- Contact resistance: 100 mΩ
- Contact activation / reset time: 100 ms
- Base terminals: 0.4 to 2 mm²; relay terminals: up to 1.5 mm²
- Operating temperature: -30°C to +70°C
- Humidity: 5 to 95% RH (non-condensing)