The Advanced MXS-003V is a genuine Advanced spare basecard for the MxPro 4 Mx-4400 1-4 loop analogue addressable fire alarm control panel, in the Argus Vega protocol version. The MxPro 4 range is now listed by Advanced as obsolete, and this spare allows existing installations to be maintained.
Advanced's MxPro 4 spares list notes that this basecard can be specified for Nittan Evolution protocol (add N) or Argus Vega protocol (add V); this is the V version.
Key features
- Genuine Advanced spare for the MxPro 4 Mx-4400
- Argus Vega protocol version
- Mx-4400 panel: dual flash-based processors with real-time clock and trace diagnostics
- Mx-4400 panel: backlit 240 x 64 graphical LCD
- Mx-4400 panel: up to 1,000 fire zones (200 per individual panel)
Technical specifications
-
Part code: MXS-003V
-
Manufacturer description: Spare Mx-4400 1-4 loop panel basecard (Argus Vega protocol)
-
For use with: MxPro 4 Mx-4400 1-4 loop panel
-
Protocol: Argus Vega
-
Panel loops: 1-4, expandable via plug-in loop drivers
-
Panel sounder circuits: 4 x 1A programmable
-
Panel battery capacity: 24V 18Ah internal, 24V 48Ah external
-
Panel loop current: 500mA
-
Panel on-board relays: 2 x 1A 30V AC/DC programmable
-
Panel auxiliary supply: 1 x 24V 500mA
-
Panel logic outputs: 8 x programmable open collector
-
Panel switch inputs: 8 volt-free digital inputs
-
Panel serial port: 1 x RS232
-
Panel event log: 1,000 fire and event plus diagnostic