| Stock available | Qty | Delivery |
|---|---|---|
| Poole | 1 | Next working day |
| UK Hub | 2 | 2 to 3 working days |
- 4 fire zones (expandable to 12)
- Conventional or Twin Wire (Sav-Wire) zone circuits, selectable by DIL switch
- Two monitored sounder circuits as standard
- Fire and fault volt-free changeover relays, plus fire and fault switched negative outputs
- Class change and alert programmable inputs
- Dependency modes A, B and C
Frequently bought together




Product details
The Advanced QZXL-4 QuickZone XL is a 4-zone conventional / Twin Wire (Sav-Wire) fire alarm control panel with integral power supply and space for standby batteries, approved to EN 54-2 and EN 54-4. It can be expanded up to 12 zones with modular expansion zone cards. The panel is easy to install and maintain and simple for the end user to operate.
Level 2 controls include Resound, Silence and Reset, plus disable and test modes; Level 3 allows sounder resound options, dependency settings, buzzer volume, the event log and panel-wide settings such as access codes and delays. It supports an extensive range of conventional fire detectors, including Apollo, Argus, Hochiki and Nittan; Twin Wire mode requires special 'Sav-Wire' detector bases and polarised 470 ohm call points.
Key features
- 4 fire zones (expandable to 12)
- Conventional or Twin Wire (Sav-Wire) zone circuits, selectable by DIL switch
- Two monitored sounder circuits as standard
- Fire and fault volt-free changeover relays, plus fire and fault switched negative outputs
- Class change and alert programmable inputs
- Dependency modes A, B and C
- Test mode, with or without sounders
- Integral detector removal monitoring
- Key switch or code entry for activation of controls
- Integral 3A switch mode PSU with space for up to 2 x 7.0Ah batteries
- Can support up to 8 fully functional repeater panels
- Modular expansion zone cards available
- Alarm load of 2.4A shared across all sounder outputs
Technical specifications
- Number of fire zones: 4 (4 to 12 with expansion)
- Zonal circuit configuration: Conventional or Twin Wire (selectable by DIL switches)
- Controls: 3 colour-coded buttons (Resound, Silence and Reset), 1-4 numerical buttons and Enter
- Key switch input: Level 2 access enable key switch or code entry
- On-board sounder circuits: 2 monitored (1A resettable fuse); a further two available with the high specification card
- On-board relays: 2 auxiliary clean changeover relays (1 Fire, 1 Fault), 3A max at 30V DC
- Mains supply: 230V 50Hz (+10% / -15%), 1.2A max
- Auxiliary supply: 28V DC 400mA continuous
- Programmable inputs: Class change and alert
- Battery capacity: 2 x 7.0Ah 12V SLA, internal
- Charger current: 1.34A (27.0V DC at 20°C, temperature compensated)
- Networking: Fully functional repeater panel via plug-in communications PCB
- Enclosure: Lockable steel, IP30, RAL 7035
- Cable entries: 20 x top, 8 x rear, 4 x base (20mm knockouts)
- Dimensions (H x W x D): Back box 300 x 450 x 85mm; door 310 x 460 x 25mm
- Approvals: EN 54-2:1997 + A1:2006; EN 54-4:1997 + A1:2002 + A2:2006