Eaton Cooper Addressable Device Programmer (CF800PROG)
£621.90
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
Key featuresFull details
- Built-in Cooper addressable detector base, so detectors can be addressed and tested simply by fitting them to the programmer
- Two external terminals (S+ and S-) for connecting addressable interfaces, call points, sounders and AV devices
- Read, write and delete device addresses
- Read analogue values and device type
- Test function lights the device LED to confirm operation
- Programs the three heat detector settings: rate of rise (A1R), fixed 77°C (BS) and fixed 92°C (CS)
Frequently bought together

Eaton
Eaton Cooper Addressable Loop Tester Kit (LP800KIT)
Sale price£627.90
Out of stock. Lead time 2 to 6 weeks, estimate only
Eaton
Eaton Cooper Addressable Panel / Interface Programmer (USBINT2)
Sale price£149.20
Out of stock. Lead time 2 to 6 weeks, estimate only
Eaton
Eaton Cooper Addressable Zone Monitor Unit (Intrinsically Safe) (CZMU352-IS)
Sale price£133.55
Out of stock. Lead time 2 to 6 weeks, estimate only
Eaton
Eaton Cooper Intelligent Addressable Ceiling VAD (Red Flash, Shallow Base) (CAB482CS)
Sale price£53.55
Out of stock. Lead time 2 to 6 weeks, estimate only
Eaton
Eaton Cooper Intelligent Addressable Ceiling VAD (White Flash, Shallow Base) (CAB492CS)
Sale price£53.55
Out of stock. Lead time 2 to 6 weeks, estimate onlyProduct details
The Eaton Cooper CF800PROG is a hand-held programmer for Cooper (now Eaton) series 800 intelligent addressable devices. It is used during installation, commissioning, maintenance and servicing to set and check device addresses, read analogue values and test devices before or after they go on the loop.
Key features
- Built-in Cooper addressable detector base, so detectors can be addressed and tested simply by fitting them to the programmer
- Two external terminals (S+ and S-) for connecting addressable interfaces, call points, sounders and AV devices
- Read, write and delete device addresses
- Read analogue values and device type
- Test function lights the device LED to confirm operation
- Programs the three heat detector settings: rate of rise (A1R), fixed 77°C (BS) and fixed 92°C (CS)
- Simple five-key operation with a menu-driven 2 x 40 character LCD display
- Light and robust for use on site
Technical specifications
- Compatibility: Cooper/Eaton series 800 addressable devices
- Display: 2 x 40 character LCD
- Power: single PP3 heavy-duty battery or external 9 V, 200 mA supply
- Controls: Power, Reset, Exit, Enter and Next keys
- Connection: one device at a time, via the built-in base or the S+/S- terminals