The EMS SmartCell Wireless Dual Input / Output Device (SC-41-0200-0001-99) provides two resistor-monitored inputs and two voltage-free outputs on the SmartCell wireless fire system. It can be used to monitor equipment such as beam or gas detection and to switch plant such as fans or gas shut-off valves, without running cables back to the panel.
It works with the SmartCell control panel and SmartCell WZM, and has an application label so connected circuits can be identified.
Key features
- 2 x resistor-monitored inputs: monitor normal, alarm, open-circuit and closed-circuit conditions
- 2 x voltage-free outputs rated 1 A at 30 VDC
- Six indication LEDs for input, output and fault status
- Fully wireless, battery powered
- Optional gasket for additional protection
- Batteries included (not included in some regions)
Technical specifications
- Power supply: 3 x 3.6 V lithium thionyl chloride batteries (Fanso or HCB ER14505M)
- Operating voltage: 2.7 to 3.65 VDC
- Output rating: 1 A at 30 VDC (maximum cable length 10 m)
- End-of-line resistor: 20 kΩ (factory fitted)
- Minimum input detection time: 2 seconds
- Operating frequency: 868 MHz
- Output transmitter power: 14 dBm / 25 mW
- Signalling protocol: X5
- Operating temperature: -10 to +55 °C
- Storage temperature: -10 to +30 °C with batteries, -10 to +55 °C without
- Humidity: 0 to 95% non-condensing
- Location: Type A, indoor use
- Dimensions (W x H x D): 150 x 200 x 55 mm
- Approvals: EN54-13, EN54-18 and EN54-25 (CPR 0359-CPR-00269)