Shop all Gent
GENT S-Cubed Addressable High Power VAD (Red Body, Red Flash) (S3-VAD-HPR-R)
SKU: S3-VAD-HPR-RBrand: Gent
| Stock available | Qty | Delivery |
|---|---|---|
| Poole | 1 | Same day dispatch |
| UK Hub | 0 | None at UK Hub |
Need help choosing?
Our UK team can check compatibility, stock and project pricing for you.
0113 518 0540info@jemsystems.co.uk
GENT S-Cubed Addressable High Power VAD (Red Body, Red Flash) (S3-VAD-HPR-R)
£78.15
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
Key featuresFull details
- EN 54-23 VAD with adjustable light coverage
- High, medium and low power settings
- Loop powered, with very low power consumption
- Active background monitoring of the VAD circuit
- Red body with red flash
Frequently bought together


Gent
Gent S4-711-V-VAD-LPR Dual Optical Heat Sensor Voice Sounder Red VAD
Sale price£117.70
In stock
Gent
GENT Vigilon Addressable Manual Call Point with Resettable Element & Cover (No Backbox) (S4-34845)
Sale price£60.10
Out of stock. Lead time 2 to 6 weeks, estimate onlyProduct details
The GENT S3-VAD-HPR-R is an S-Cubed loop-powered, high-power visual alarm device (VAD) with a red body and red flash, for Gent Vigilon fire alarm systems. It is certified to EN 54-23, and its light output can be adjusted between high, medium and low power settings to suit the area it covers.
Key features
- EN 54-23 VAD with adjustable light coverage
- High, medium and low power settings
- Loop powered, with very low power consumption
- Active background monitoring of the VAD circuit
- Red body with red flash
Technical specifications
- Order code: S3-VAD-HPR-R
- VAD category: high performance
- Coverage (red): W-6.7-14 (high), W-6.5-12.5 (medium), W-5-9.5 (low)
- Approx. max quantity per loop (dependent on loop load): high power 44, medium 57, low 100
- Strobe flash rate: 0.5 Hz
- Operating temperature: -10°C to +50°C
- Ingress protection: IP21 (standard range)
- Approx. weight: 0.3 kg
- Approvals: EN 54-23:2010, EN 54-17