Shop all Kentec Electronics

Kentec Dual Power Output PCB Retrofit Kit - RPSM2 (K738)

SKU: K738Brand: Kentec Electronics
4.7store rating from 109 reviews
Available to order Qty Delivery
Pre-order0Lead time 2 to 6 weeks
Price:
Sale price£39.85
47.82 inc. VAT39.85 ex VAT
Stock:
Pre-Order (Not in Stock) - Estimated Lead Time: 2-6 Weeks.
Delivery
2 to 6 weeks
Ordered in for you
Collect in Poole
Not stocked in Poole
Delivery only
Kentec Dual Power Output PCB Retrofit Kit - RPSM2 (K738) £39.85
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
American Express Apple Pay Google Pay KlarnaMaestroMastercard PayPalShop Pay Visa
Key featuresFull details
  • Two independent 24V DC outputs (OUT1 and OUT2) to the two power inputs of the control panel
  • A short or open circuit on one transmission path leaves the panel supplied through the other
  • Common fault relay, normally energised, signals any power supply fault including failure of a transmission path or total power failure
  • Connects to the power supply by ribbon cable for power and fault signals
  • For use only with control equipment that has two separate 24V DC inputs

Frequently bought together

Kentec Economy Software Download Lead (X187LS) - JEM Systems UK
Kentec 4-Way Relay Unit
Kentec Electronics Kentec K143031 4-Way Relay Unit
Sale price£171.55
Pre-Order (Not in Stock) - Estimated Lead Time: 2-6 Weeks.
Kentec KB2869 Thermal Printer Paper Roll, 57mm, 20-PackKentec KB2869 Thermal Printer Paper Roll, 57mm, 20-Pack

Product details

The Kentec RPSM2 dual power output PCB provides two separate transmission paths between a Kentec K25000 series power supply and the fire alarm control and indicating equipment it feeds, so that power continues to reach the control panel if one path fails. This satisfies clause 6.4 of EN54-4 for power supply equipment mounted in a separate enclosure to the control panel. The RPSM2 is the board fitted as standard to Kentec's KD models; this kit allows it to be retrofitted.

Key features

  • Two independent 24V DC outputs (OUT1 and OUT2) to the two power inputs of the control panel
  • A short or open circuit on one transmission path leaves the panel supplied through the other
  • Common fault relay, normally energised, signals any power supply fault including failure of a transmission path or total power failure
  • Connects to the power supply by ribbon cable for power and fault signals
  • For use only with control equipment that has two separate 24V DC inputs

Technical specifications

  • Compatible power supplies: Kentec K25000 series (K25250 and K25400 models)
  • Total load over both outputs: 5A max on K25400 models, 3.5A max on K25250 models
  • Fuses: FF very fast acting 6.3A (replace only with the same type)
  • Standard: EN54-4 clause 6.4