Shop all Kentec Electronics
Kentec Dual Power Output PCB Retrofit Kit - RPSM2 (K738)
SKU: K738Brand: Kentec Electronics
| Available to order | Qty | Delivery |
|---|---|---|
| Pre-order | 0 | Lead time 2 to 6 weeks |
Kentec Dual Power Output PCB Retrofit Kit - RPSM2 (K738)
£39.85
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
Key featuresFull details
- Two independent 24V DC outputs (OUT1 and OUT2) to the two power inputs of the control panel
- A short or open circuit on one transmission path leaves the panel supplied through the other
- Common fault relay, normally energised, signals any power supply fault including failure of a transmission path or total power failure
- Connects to the power supply by ribbon cable for power and fault signals
- For use only with control equipment that has two separate 24V DC inputs
Frequently bought together

Kentec Electronics
Kentec K143031 4-Way Relay Unit
Sale price£171.55
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

Kentec Electronics
Kentec K67000M1 Syncro View Local LCD Repeater Panel without Power Supply
Sale price£393.35
In stock

Kentec Electronics
Kentec KB2869 Thermal Printer Paper Roll, 57mm, 20-Pack
Sale price£109.85
In stock
Kentec Electronics
Kentec KL11040M2 Sigma CP 4 Zone Conventional Fire Alarm Control Panel
Sale price£272.15
In stockProduct details
The Kentec RPSM2 dual power output PCB provides two separate transmission paths between a Kentec K25000 series power supply and the fire alarm control and indicating equipment it feeds, so that power continues to reach the control panel if one path fails. This satisfies clause 6.4 of EN54-4 for power supply equipment mounted in a separate enclosure to the control panel. The RPSM2 is the board fitted as standard to Kentec's KD models; this kit allows it to be retrofitted.
Key features
- Two independent 24V DC outputs (OUT1 and OUT2) to the two power inputs of the control panel
- A short or open circuit on one transmission path leaves the panel supplied through the other
- Common fault relay, normally energised, signals any power supply fault including failure of a transmission path or total power failure
- Connects to the power supply by ribbon cable for power and fault signals
- For use only with control equipment that has two separate 24V DC inputs
Technical specifications
- Compatible power supplies: Kentec K25000 series (K25250 and K25400 models)
- Total load over both outputs: 5A max on K25400 models, 3.5A max on K25250 models
- Fuses: FF very fast acting 6.3A (replace only with the same type)
- Standard: EN54-4 clause 6.4