Shop all Kentec Electronics

Kentec Sigma CP-A 4 Zone Alarmsense Fire Panel (KA11040M2)

SKU: KA11040M2Brand: Kentec Electronics
4.7store rating from 111 reviews
Stock available Qty Delivery
Poole0None in Poole
UK Hub121 to 3 working days
Need help choosing? Our UK team can check compatibility, stock and project pricing for you. 0113 518 0540info@jemsystems.co.uk
Price:
Sale price£363.30
435.96 inc. VAT363.30 ex VAT
Stock:
In stock (12 units)
Delivery
1 to 3 working days
Ships from our UK supplier hub
Collect in Poole
Not stocked in Poole
Delivery only
Kentec Sigma CP-A 4 Zone Alarmsense Fire Panel (KA11040M2) £363.30
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
American Express Apple Pay Google Pay KlarnaMaestroMastercard PayPalShop Pay Visa
Key featuresFull details
  • Complies with EN54-2 and EN54-4
  • Four AlarmSense zones for Apollo AlarmSense detectors, call points, sounder bases, sounder beacon bases and alarm relays
  • Priority/non-priority sounder scheme: sounders can be set so that only the sounder near the activated detector operates first, subject to a configurable alarm verification period; ideal for Houses of Multiple Occupation and full compliance with BS 5839-6
  • Configurable alarm verification delay of 30, 60 or 120 seconds
  • Two common (conventional) sounder circuits in addition to the zonal sounders
  • Volt-free fire, local fire and fault relay contacts

Frequently bought together

Kentec Sigma CP-A 8 Zone Alarmsense Fire Panel (KA11080M2) - JEM Systems UK
Kentec Sigma CP-A Replacement Panel PCB 2-Wire 8 Zone
Kentec Electronics Kentec Sigma CP-A Replacement Panel PCB 2-Wire 8 Zone
Sale price£288.40
Out of stock. Lead time 2 to 6 weeks, estimate only
Kentec Sigma CP-R 2 Zone Conventional Repeater Panel no PSU
Kentec Electronics Kentec Sigma CP-R 2 Zone Conventional Repeater Panel no PSU
Sale price£177.65
Out of stock. Lead time 2 to 6 weeks, estimate only
Kentec Sigma CP-R 2 Zone Repeater Panel - 230v (K01020M2) - JEM Systems UK
Kentec Electronics Kentec Sigma CP-R 2 Zone Repeater Panel - 230v (K01020M2)
Sale price£273.60
Out of stock. Lead time 2 to 6 weeks, estimate only
Kentec Sigma CP-R 2 Zone Replacement Panel PCB 230V
Kentec Electronics Kentec Sigma CP-R 2 Zone Replacement Panel PCB 230V
Sale price£135.85
Out of stock. Lead time 2 to 6 weeks, estimate only

Product details

The Kentec Sigma CP-A KA11040M2 is a 4 zone conventional fire alarm control panel for the Apollo AlarmSense two-wire system, certified to EN54-2 and EN54-4. AlarmSense lets compatible smoke and heat detectors, call points, sounders, sounder beacons and alarm relays share a single pair of wires on each zone, so separate sounder circuit cables are not needed. The panel has an integral, mains-powered power supply and battery charger.

Key features

  • Complies with EN54-2 and EN54-4
  • Four AlarmSense zones for Apollo AlarmSense detectors, call points, sounder bases, sounder beacon bases and alarm relays
  • Priority/non-priority sounder scheme: sounders can be set so that only the sounder near the activated detector operates first, subject to a configurable alarm verification period; ideal for Houses of Multiple Occupation and full compliance with BS 5839-6
  • Configurable alarm verification delay of 30, 60 or 120 seconds
  • Two common (conventional) sounder circuits in addition to the zonal sounders
  • Volt-free fire, local fire and fault relay contacts
  • Test mode with automatic resetting of zones for testing
  • Two seven-segment LED displays and MODE, SELECT and ENTER buttons for configuration
  • Connections for repeater panels, ancillary boards and 8-way sounder boards

Technical specifications

  • Zones: 4 (AlarmSense)
  • Mains supply: 230V AC +10%/-15% (100W max)
  • Power supply rating: 3A total including battery charge
  • Output voltage: 18.5 to 29V DC
  • Batteries: two 12V sealed lead acid, 7Ah max
  • Standby battery for a fully loaded panel: 3.3Ah (24h), 5.1Ah (48h), 6.9Ah (72h)
  • Standby current: 0.075A; max panel alarm current: 0.21A
  • Detectors per zone: up to 20
  • Dedicated sounder outputs: 24V, 500mA each; zonal sounder outputs: 24V, 200mA; 1.6A total across all circuits
  • Relay contacts (fire, local fire, fault): 30V DC 1A max
  • Detection circuit EOL: 3k3 resistor; sounder circuit EOL: 10k resistor (supplied)
  • Terminal capacity: 0.5mm² to 2.5mm²
  • IP rating: IP30
  • Operating temperature: -5°C to +40°C, max 95% relative humidity
·