A Talentum 16000 series IR2 flame detector for protecting areas where open fires may occur. It responds to the flickering, low-frequency (1-15 Hz) infrared radiation given off by flames, using two IR sensors at different wavelengths to tell real fires from other sources of radiation.
Key features
- Dual IR sensing for high immunity to false alarms, including flickering sunlight
- Detects almost all flames, from hydrocarbon fires through to invisible hydrogen fires
- Works even if the window is contaminated by oil, dust, water vapour or ice
- Detects flames through glass; unaffected by draughts or wind
- Selectable sensitivity, response speed and output (relay contacts or 4-20 mA)
- Built-in automatic and manual test
Specification
| Product code |
16581-00 |
| Brand |
Talentum |
| Detector type |
IR2 (dual infrared) flame detector |
| Housing |
Die-cast zinc alloy, blue |
| Dimensions |
142 (h) x 108 (w) x 79 (d) mm |
| Weight |
1.75 kg |
| Supply voltage |
14 to 30 Vdc |
| Relay rating |
0.75 A, 48 Vdc, 30 W (resistive) |
| Operating temperature |
-10 to +55 °C |
| IP rating |
IP65 |
| Range |
0.1 m² n-heptane at 25 m (Class 1) / 12 m (Class 3) |
| Field of view |
90° minimum cone |
| Approvals |
EN54-10, LPCB |