Shop all VESDA by Xtralis

VESDA VHX-1300 Metal Box High Level Interface (Peer to Peer)

SKU: VHX-1300Brand: VESDA by Xtralis
4.7store rating from 108 reviews
Available to order Qty Delivery
Pre-order0Lead time 2 to 6 weeks
Price:
Sale price£2,133.85
2,560.62 inc. VAT2,133.85 ex VAT
Stock:
Pre-Order (Not in Stock) - Estimated Lead Time: 2-6 Weeks.
Delivery
2 to 6 weeks
Ordered in for you
Collect in Poole
Not stocked in Poole
Delivery only
VESDA VHX-1300 Metal Box High Level Interface (Peer to Peer) £2,133.85
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
American Express Apple Pay Google Pay KlarnaMaestroMastercard PayPalShop Pay Visa
Key featuresFull details
  • Peer-to-peer Open Protocol communication over RS-232
  • Built-in VESDAnet interface; wall-mounted metal enclosure
  • Reports detector type, alarm status (Alert, Action, Fire 1, Fire 2), fault status, isolate/normalising/AutoLearn/scanning status, smoke level and fault details
  • Detector controls: reset, isolate, silence, test, scan
  • Recommended by Xtralis for secondary monitoring; for primary reporting the HLI must be integrated and approved/listed with the relevant fire panel or reporting system

Frequently bought together

VESDA by Xtralis VHX-1420 - JEM Systems UK
VESDA by Xtralis VESDA VHX-1420 Metal Box High Level Interface (Modbus Type 3)
Sale price£2,182.25
Pre-Order (Not in Stock) - Estimated Lead Time: 2-6 Weeks.
Vesda VLF-500-00 VLF European language set. English display labels - JEM Systems UKVesda VLF-500-00 VLF European language set. English display labels - JEM Systems UK
VESDA by Xtralis VLI-885 - JEM Systems UK
VESDA by Xtralis VESDA VLI-885 LaserINDUSTRIAL Aspirating Detector with VESDAnet
Sale price£5,911.20
Pre-Order (Not in Stock) - Estimated Lead Time: 2-6 Weeks.

Product details

The Xtralis VESDA VHX-1300 is a wall-mounted Open Protocol High Level Interface (HLI) in a metal box, using the peer-to-peer model. It links a VESDAnet network with PC monitoring software, building management systems (BMS) or fire alarm control panels (the "host"). In the peer-to-peer model the host polls the HLI for information and the HLI also sends unsolicited messages, so both supervise the link; the host can request and receive multiple messages. Its built-in VESDAnet interface means no separate VESDAnet socket module is needed.

Key features

  • Peer-to-peer Open Protocol communication over RS-232
  • Built-in VESDAnet interface; wall-mounted metal enclosure
  • Reports detector type, alarm status (Alert, Action, Fire 1, Fire 2), fault status, isolate/normalising/AutoLearn/scanning status, smoke level and fault details
  • Detector controls: reset, isolate, silence, test, scan
  • Recommended by Xtralis for secondary monitoring; for primary reporting the HLI must be integrated and approved/listed with the relevant fire panel or reporting system

Technical specifications

  • Part number: VHX-1300 (Open Protocol HLI, Peer-to-Peer)
  • Power consumption: 1.68 W (quiescent)
  • Supply voltage: 24 VDC
  • Current consumption: 70 mA (quiescent)
  • Dimensions: 280 x 185 x 55 mm (approx.)
  • Weight: 2 kg
  • Detectors supported: up to 40
  • Modem support: not available

What's in the box

  • VESDAlink RS-232 9-way serial cable (male-female), identical to VSP-509

Datasheet