The Zeta Fyreye MKII-HR is a conventional rate-of-rise heat detector (EN 54-5 Class A1R) for use on conventional fire alarm zones. A thermistor arrangement senses a rapid rise in temperature and also gives a final fixed threshold alarm at 57°C.
Key features
- Rate of rise plus 57°C fixed heat threshold
- Designed to meet EN 54 requirements
- Lockable to base to prevent unauthorised removal
- Remote LED output
- Compatible with all Fyreye bases: standard or deep, with or without diode (MKII-CB, MKII-CB/D, MKII-DB, MKII-DB/D)
Technical specifications
- Part number: 80-202
- Detector class: rate of rise and fixed heat, EN 54-5
- Operating voltage: 9 to 33 V DC
- Quiescent current: 40 µA; alarm current 34 mA at 24 V DC
- Alarm condition: rate of rise or fixed heat trigger at 57°C
- Coverage: 50 m²
- Operating temperature: -10°C to +50°C
- Max humidity: 95% RH non-condensing
- IP rating: IP43
- Start-up time: 10 seconds
- Size with base: 100 x 48 mm