The Advanced MXP-505 Sounder Active EOL is a small, compact active end-of-line unit that provides active monitoring of sounder circuits on MxPro 5 series fire alarm control panels, allowing the circuits to be configured for compliance with EN 54-13.
To comply with EN 54-13, the system must check and warn, before an alarm condition, if the voltage at the last device cannot be maintained under the applied alarm load. To meet this requirement the Sounder Active EOL must be fitted to, and programmed for, all panel sounder outputs. It is designed to be terminated and housed in third-party sounder output devices.
Key features
- For use in EN 54-13 compliant systems
- Active monitoring of panel sounder circuits
- Supports device removal
- Small and compact; fits inside third-party sounder output devices
- Simple to install
- For use with all MxPro 5 series control panels
Technical specifications
-
Part code: MXP-505
-
Type: Sounder active end-of-line device for EN 54 part 13
-
Requirement: One per panel sounder output for EN 54-13 compliance
-
Compatibility: All MxPro 5 series control panels