The EMS FireCell Wireless Detector Base c/w Remote Indicator Unit, part number FCX-170-101, is a FireCell wireless detector base supplied with a hard-wired remote indicator unit. The remote indicator unit is connected to the base by cable and provides a remote indication for the detector fitted to that base. A FireCell wireless detector head fits into the base.
It works with FireCell systems, the Fusion RLM and the EMS WZM, and is addressed through the control panel's user interface.
Key features
- Wireless detector base with remote indicator unit
- Remote indicator cabling can be extended up to 30 m using a closed electrical connector
- One detector per remote indicator unit
- Detector can be locked into the wireless module with a 1.5 mm Allen key
- Third party EN54-25 certified
Technical specifications
- Part number: FCX-170-101 (wireless detector base c/w remote indicator unit)
- Power supply: 6 x AA alkaline (Panasonic LR6AD Powerline / Varta 4006 Industrial)
- Operating frequency: 868 MHz; output power auto adjusting 0 to 14 dBm (0 to 25 mW)
- Signalling protocol: X
- Maximum remote indicator cable length: 30 m
- Operating temperature: -10 to +55 °C; storage: 5 to 30 °C
- Humidity: 0 to 95% non-condensing
- IP rating: IP23; Type A indoor use
- Dimensions: remote indicator unit 85 x 85 x 45 mm (H x W x D); detector base 113 mm diameter x 40 mm depth
- Weight: 0.15 kg (remote indicator unit); 0.40 kg (wireless detector complete)
- Approval: EN54-25 (0359-CPR-0041)