The AirSense Stratos HSSD2 (9-30621) is a large-area, high-sensitivity aspirating smoke detector (ASD) designed to give the very earliest warning of incipient fire with a minimum rate of nuisance alarms. It takes up to four sampling pipes with up to 200 m of combined pipe and covers areas of up to 2000 m².
ClassiFire artificial intelligence automatically sets the detector to the best sensitivity for the protected area, from high sensitivity in a computer room to reduced sensitivity in a smoky area. It has an LCD and keypad, five relay outputs and RS-485 SenseNET networking. Typical applications include data storage, computer rooms, equipment racks, plant and motor rooms, air-conditioning units, prison cells and heritage properties.
Key features
- Laser-based forward light scatter for reliable early warning
- Up to 200 m combined sampling pipe (100 m single run in still air)
- Coverage of up to 2000 m²
- ClassiFire perceptive artificial intelligence and LDD laser dust discrimination
- LED and LCD status indication with keypad
- RS-485 SenseNET networking: up to 127 detectors per loop; APIC cards, Command Module and remote displays available
- CPR, LPCB, VdS, NF, CSIRO, UL and FM approved
Technical specifications
- Detection principle: laser light scattering mass detection and particle evaluation
- Sensitivity range: 0.0015 to 25 %obs/m
- Particle sensitivity range: 0.003 to 10 microns
- Alarm levels: 4 (Aux, Pre-alarm, Alarm, Alarm 2)
- Sampling pipe: 100 m maximum single run (50 m in moving air), 200 m combined
- Inlets: 4; pipe diameter 27 mm OD
- Sampling holes: up to 100
- Exhaust: 1 (optional)
- Inputs: 3 programmable
- Outputs: 5 (Pre-alarm, Alarm, Alarm 2, Aux (NO) and Fault (NC)), 500 mA at 30 V
- Operating voltage: 21.6 to 26.4 VDC
- Current consumption: 450 mA at fan speed 8
- Dimensions: 427 x 372 x 95 mm (W x H x D)
- Weight: 5.2 kg
- Enclosure: sheet steel with plastic front cover, cream
- Mounting: wall mount
- Cable entries: 6 x M20
- Operating temperature: -10 to +60°C
- Relative humidity: 0 to 90% non-condensing
- Environment: indoor, IP40
- Certification: EN 54-20, FM, UL