The Fike 404-0006 is a standalone, battery-operated manual call point with a built-in sounder. It raises a local alarm without a fire alarm panel. It is not compatible with conventional, 2-wire or addressable systems. Up to twelve units can be linked together, and any activated call point powers the sounders on the others.
Key features
- Self-contained battery operation, with no panel or mains supply needed
- Built-in sounder with dual-tone UK evacuate tone
- Resettable element that latches when operated and is reset with the key
- Link up to 12 units
- Surface mounting back box, or flush mounting with the optional adaptor plate and a standard single-gang box (minimum 47 mm internal depth)
- Fike recommends yearly battery replacement and weekly testing
Technical specifications
- Dimensions (W x H x D): 87 x 87 x 53 mm
- Power source: 2 x 23A 12 V cells per unit
- Operating voltage: 24 V DC
- Operating current: 0 A quiescent; 11.1 mA in alarm (dual-tone UK)
- Sound output: 85 dB(A)
- Operating temperature: -10°C to +50°C
- Flammability: UL94-V2; IP21C
- Maximum interconnected units: 12