The Global Fire Equipment VULCAN 2 ABI is an addressable base beacon with a built-in loop isolator, listed here in black (VULCAN2-ABI-BLK). It is a detector base with a visual alarm, for GFE addressable fire alarm panels such as the G-One, GEKKO and OCTO+.
It can be set up in the field as a shadow device, with no address of its own so more addresses are free for detectors, or as an auxiliary device that shares the address of the detector fitted on it. Addresses are set with DIP switches.
Key features
- Detector base beacon with built-in loop isolator
- Shadow or auxiliary operating modes, set by jumper
- DIP-switch addressing
- Optional lid for use without a detector
Technical specifications
- Quiescent loop current: 550 µA max. (with isolator)
- Beacon current: 2.7 mA (beacon with isolator)
- Supply voltage: loop powered, 20 V to 30 V DC
- Cable size: 0.5 to 2.5 mm²
- Reset/start-up time: 20 seconds max.
- Protection: IP21C, Type A indoor use
- Case material: ABS with transparent PC
- Operating temperature: -10°C to 55°C; humidity 95% RH non-condensing
- Dimensions: 110 (D) x 50 (H) mm including base