Shop all VESDA by Xtralis
VESDA VHX-0300 PC Link High Level Interface (Open Protocol)
SKU: VHX-0300Brand: VESDA by Xtralis
| Available to order | Qty | Delivery |
|---|---|---|
| Pre-order | 0 | Lead time 2 to 6 weeks |
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
Key featuresFull details
- Peer-to-peer communication: both the HLI and the host supervise the link; the host can request and receive multiple messages
- Reports detector type (VLC, VLS, VLP, VLF) and supports Mimic Mode for VLP/VLC/VLS
- Alarm status (Alert, Action, Fire 1 and Fire 2) and fault status (system, zone, urgent, power, network, flow, filter)
- Detector status (isolated, normalising, AutoLearn, scanning), display information and smoke level updates
- Fault details with ASCII fault strings, plus detector controls (reset, isolate, silence, test, scan)
- Direct access to, and monitoring of, the VESDAnet system
Frequently bought together

VESDA by Xtralis
VESDA VHX-0420 PC Link Modbus High Level Interface (MK3)
Sale price£1,146.50
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

VESDA by Xtralis
VESDA VHX-1200 High Level Interface with VESDAnet Socket in Enclosure
Sale price£1,074.75
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

VESDA by Xtralis
VESDA VHX-1300 Metal Box High Level Interface (Peer to Peer)
Sale price£2,133.85
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.
Product details
The Xtralis VHX-0300 is the VESDA Open Protocol High Level Interface (HLI), peer-to-peer version. It links a VESDAnet network of VESDA detectors to a host such as PC monitoring software, a building management system (BMS) or a fire alarm control panel (FACP). In the peer-to-peer model the host polls the HLI for information, while the HLI can also send unsolicited messages to the host.
Key features
- Peer-to-peer communication: both the HLI and the host supervise the link; the host can request and receive multiple messages
- Reports detector type (VLC, VLS, VLP, VLF) and supports Mimic Mode for VLP/VLC/VLS
- Alarm status (Alert, Action, Fire 1 and Fire 2) and fault status (system, zone, urgent, power, network, flow, filter)
- Detector status (isolated, normalising, AutoLearn, scanning), display information and smoke level updates
- Fault details with ASCII fault strings, plus detector controls (reset, isolate, silence, test, scan)
- Direct access to, and monitoring of, the VESDAnet system
- Seamless data transfer
- Easily configured using Xtralis configuration and monitoring software
- VESDAnet is a fault-tolerant, bi-directional protocol: if one direction of communication fails, messages are sent the other way
- Recommended for secondary monitoring; also suitable for primary reporting when integrated and approved/listed with the relevant fire panel
Technical specifications
- Part number: VHX-0300 (Open Protocol HLI, peer-to-peer)
- Supply voltage: 24 VDC
- Current consumption: 70 mA (quiescent); power 1.68 W
- Dimensions: 188 mm x 98 mm x 40 mm
- Weight: 0.4 kg
- Detectors supported: up to 40
- Modem support: not available
- Master-slave version: VHX-0310
What's in the box
- VESDAlink RS-232 9-way serial cable (male–female)
- VESDAnet RS-485 15-way cable (male–female)






