Shop all VESDA by Xtralis
VESDA VHX-1410 Metal Box High Level Interface (Modbus Type 2)
SKU: VHX-1410Brand: VESDA by Xtralis
| Available to order | Qty | Delivery |
|---|---|---|
| Pre-order | 0 | Lead time 2 to 6 weeks |
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
Key featuresFull details
- Links VESDAnet to a BMS, fire alarm control panel or PC monitoring tool that supports the Modbus protocol
- Reports detector type, alarm state (Alert, Action, Fire), smoke level, bar graph level and alarm thresholds
- Fault status reporting: head, battery and mains, flow and scanner faults
- Host can reset or isolate detectors and start a scan test (VLS only)
- Wall-mounted unit with fixing points (6.5 mm)
- Recommended for secondary monitoring; can be used for primary reporting when integrated and approved with the relevant fire panel
Frequently bought together

VESDA by Xtralis
VESDA VHX-1420 Metal Box High Level Interface (Modbus Type 3)
Sale price£2,182.25
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

VESDA by Xtralis
VESDA VLF-250-00 LaserFOCUS Small Area Aspirating Detector (25m Pipe)
Sale price£1,175.70
In stock

VESDA by Xtralis
VESDA VLF-500-00 VLF-500 LaserFOCUS Aspirating Smoke Detector (European Language Set, English Display Labels)
Sale price£1,563.10
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

VESDA by Xtralis
VESDA VLI-885 LaserINDUSTRIAL Aspirating Detector with VESDAnet
Sale price£5,911.20
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.

VESDA by Xtralis
VESDA VPS-220-E5 Power Supply (FM Approved) - Style E
Sale price£258.30
Pre-Order (Not in Stock)
- Estimated Lead Time: 2-6 Weeks.
Product details
The Xtralis VESDA VHX-1410 is a wall-mounted Modbus High Level Interface (HLI), Type 2. It links a VESDAnet network of VESDA detectors to host systems such as building management systems (BMS) and fire alarm control panels that support the Modbus protocol. The Type 2 version has the character echo function disabled.
Key features
- Links VESDAnet to a BMS, fire alarm control panel or PC monitoring tool that supports the Modbus protocol
- Reports detector type, alarm state (Alert, Action, Fire), smoke level, bar graph level and alarm thresholds
- Fault status reporting: head, battery and mains, flow and scanner faults
- Host can reset or isolate detectors and start a scan test (VLS only)
- Wall-mounted unit with fixing points (6.5 mm)
- Recommended for secondary monitoring; can be used for primary reporting when integrated and approved with the relevant fire panel
Technical specifications
- Part number: VHX-1410 (Modbus HLI Type 2)
- Supply voltage: 24 VDC
- Current consumption: 70 mA (quiescent)
- Power consumption: 1.68 W (quiescent)
- Dimensions: 280 x 185 x 55 mm (approx.)
- Weight: 1.0 kg
- Devices supported: up to 200 VESDA devices, including a maximum of 40 detectors
- Detector zone numbers supported: 1 to 200
- Host link: RS-232
- Modem support: not available
What's in the box
- Wall-mounted Modbus HLI
- VESDAlink RS-232 9-way serial cable (male to female)