Shop all Zeta
Zeta SmartConnect Multi-Loop Conventional Sounder Circuit Module (2 Circuits) (SCM-ACM)
SKU: SCM-ACMBrand: Zeta
| Out of stock | Qty | Delivery |
|---|---|---|
| All locations | 0 | Lead time 2 to 6 weeks, estimate only |
Need help choosing?
Our UK team can check compatibility, stock and project pricing for you.
0113 518 0540info@jemsystems.co.uk
Zeta SmartConnect Multi-Loop Conventional Sounder Circuit Module (2 Circuits) (SCM-ACM)
£157.30
Genuine stockBrand new, boxed
1 year warrantyPlus statutory rights
Secure checkoutEncrypted payments
Trade accounts30 day credit
Key featuresFull details
- 2 output circuits, 500mA each
- Each circuit usable as an alarm output or a power output
- Supervised for open circuit, short circuit and earth fault
- Power limited
- Extensive front status indications
- Quick to install: plugs into the panel with an RJ45 cable (cable supplied)
Frequently bought together

Zeta
Zeta SmartConnect Multi-Loop Conventional Zone Monitor (6 Circuits) (SCM-ZMM)
Sale price£177.40
Out of stock. Lead time 2 to 6 weeks, estimate only
Zeta
Zeta SmartConnect Multi-Loop Input Module (6 Inputs) (SCM-MIM)
Sale price£177.40
Out of stock. Lead time 2 to 6 weeks, estimate only
Zeta
Zeta SmartConnect Multi-Loop Multi-Relay Output Module (SCM-RM)
Sale price£157.30
Out of stock. Lead time 2 to 6 weeks, estimate only
Zeta
Zeta SmartConnect Multi-Loop RS232 Printer Module (SCM-PM)
Sale price£157.30
Out of stock. Lead time 2 to 6 weeks, estimate only
Zeta
Zeta SmartConnect Multi-Loop RS485 Network Module (SCM-NM)
Sale price£314.65
Out of stock. Lead time 2 to 6 weeks, estimate onlyProduct details
The Zeta SCM-ACM is a plug-in alarm circuit module for the Zeta SmartConnect Multi-loop fire alarm panel, providing two conventional sounder circuits of 500mA each. The circuits are supervised for open circuit, short circuit and earth fault, and either circuit can instead be programmed as a 24V auxiliary output to power external equipment.
Key features
- 2 output circuits, 500mA each
- Each circuit usable as an alarm output or a power output
- Supervised for open circuit, short circuit and earth fault
- Power limited
- Extensive front status indications
- Quick to install: plugs into the panel with an RJ45 cable (cable supplied)
Technical specifications
- Part number: 37-395
- Design standard: EN54 part 2; LPCB approved
- Output current: 2 x 500mA
- End of line: 4.7kΩ
- Operating temperature: -5°C to 40°C; humidity 95% non-condensing
- Size: 105 x 57 x 47mm (H x W x D); weight 0.15kg
- Terminal wiring size: 0.8mm² to 2.5mm²