The Advanced MXP-532F is the MxPro 5 General Routing/Protection Interface, supplied factory fitted to the panel. It is an optional card that provides monitored circuits to fire/fault routing equipment or fire protection equipment, for compliance with BS EN 54-2 clauses 7.9 and 8.9 and BS 5839-1.
Outputs are monitored for open and short circuit in both normal and active states, with faults reported on the panel display and LEDs. Two fire routing outputs let you separate manual call point and automatic detector fire signals if required. The interface connects directly to the panel's peripheral bus.
Key features
- Monitored outputs for fire/fault routing or fire protection equipment
- Two fire routing outputs to separate MCP and AFD signals
- Open and short circuit monitoring in quiescent and active states
- Drives relay coils of 1kΩ to 5kΩ
- 4 monitored inputs
- Compatible with a wide range of routing equipment
- Simple to install and configure
Technical specifications
-
Part code: MXP-532F
-
Output circuit: 24V DC active, 5V DC monitor
-
Fire and fault outputs: 1.0mA monitor mode nominal; 5.0-25.0mA active depending on coil impedance; 40.0mA max short circuit
-
Inputs: 4 x monitored, EOL 10kΩ, operating resistor 470Ω
-
Operating voltage: 24V DC (19-28V) from panel auxiliary supply output
-
Panel loading, standby (mains fail): 43mA
-
On-board indications: 6 x LEDs
-
Operating temperature: 0°C to 50°C
-
Approvals: BS EN 54-2: 1998
-
Compatibility: All MxPro 5 panels with software version 50.07 or later; PC-Configuration tool 6.12 or later