The Advanced MXP-536 is an 8-way conventional zone monitor card for MxPro 5 series fire alarm control panels. It is an optional P-Bus peripheral that adds eight individually programmable conventional zone monitor circuits, compliant with BS EN 54-18:1998 clause 7.8, to an addressable panel.
Up to 16 cards can be connected to a multi-loop panel, giving a maximum of 128 additional zone monitor circuits, and each zone can be programmed using the panel's dynamic cause-and-effect rules.
Key features
- 8 conventional zone circuits, each monitored for open and short circuit
- Each zone individually programmable with dynamic cause-and-effect rules
- Up to 16 cards per panel for a total of 128 additional zone monitor circuits
- 1 relay output for reset
- Easily configured via PC-NeT-003
- 3-year warranty as standard
Technical specifications
-
Applicable standards: BS EN 54-18 compatible
-
Zone inputs: 8 monitored inputs
-
Supply: 24V DC nominal (21-28V DC); 100mA quiescent, 500mA with all zones short circuit
-
Relay output: 1 x 24V DC, 1A
-
Fault input: Volt-free, clean contact
-
PCB weight: 75g
-
Operating temperature: -5°C to 40°C
-
Relative humidity: 95% non-condensing (max)
-
Compatibility: All MxPro 5 series control panels